Рисунок 6-10, Dgc-2020, Lo a d – Инструкция по эксплуатации Basler Electric DGC-2020

Страница 306

Advertising
background image

Типовая схема 3-фазного подключения в треугольник (Версия оборудования 3)

Рисунок 6-10. Типовая схема 3-фазного подключения в треугольник (Версия оборудования 3)

GENERATOR

≤ 480V

31

32

MPU+

MPU–

69

IA

68

IA

+

72

IB

71

IB

+

75

IC

74

IC

+

41

GEN VA

39

GEN VB

37

GEN VC

35

GEN VN

78/43

BUS VB

80

BUS VC

A

B

C

N

51

52

OUT 1

53

54

55

56

57

58

59

60

61

62

63

64

65

66

OUT 2

OUT 3

OUT 4

OUT 5

OUT 6

OUT 7

OUT 8

OUT 9

OUT 10

OUT 11

OUT 12

PRE

RUN

START

START

SOLENOID

FUEL

SOLENOID

2

BATT

3

BATT

+

1

CHASSIS

GLOW PLUGS

8

9

OIL

FUEL

10

11

COOLANT

SENDER COM

46

47

ESTOP

ESTOP

15

16

INPUT 16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

INPUT 15

INPUT 14

INPUT 13

INPUT 12

INPUT 11

INPUT 10

INPUT 8

INPUT 9

INPUT 7

INPUT 6

INPUT 5

INPUT 3

INPUT 4

INPUT 2

INPUT 1

6

RDP BATT–

7

RDP BATT+

Horn

Not in Auto

Global Alarm

Global Pre-Alarm

Open Generator Breaker

Close Generator Breaker

Open Mains Breaker

Close Mains Breaker

Governor Raise

Governor Lower

AVR Raise

AVR Lower

Emergency

Stop

Mains Bkr Status

Gen Bkr Status

Close Mains Breaker

Open Mains Breaker

Close Gen Breaker

Open Gen Breaker

P0071-59

M

P

U

GEN CKT

BKR

L1

L2

L3

N

Mechanical
Senders

12/24V

5

RDP TXD–

4

RDP TXD+

Mini-B

USB

RS-232 for

User-Supplied

External Modem

13

485

B

14

485

A

12

485

SHIELD

49

CAN H

50

SHIELD

48

CAN L

2

2

7

7

1

1

1

3

4

DGC-2020

2

Labels indicate the functions assigned by
the default programmable logic to the
contact inputs and output contacts.

1

Current inputs are 1A or 5A, depending
on style.

3

Connect near engine block (negative
battery terminal) side of senders.

4

Jumper terminals 46 and 47 if not using
an emergency stop switch. See
Emergency Stop Input section for
optional wiring methods.

7

Optional. Refer to style number for
ordering information.

MAINS CKT

BKR

L

O

A

D

76/45

BUS VA

To ECU CAN Bus

To ECU
Power or
Key-on
Terminal

5

6

Connect to ECU on electronically
controlled engines only.

If component is under ECU control, do
not connect to DGC-2020.

5

5

6

6

6

6-14

DGC-2020

Монтаж

9400273990 Bep. X1

Advertising