EN54-16: 2008 compliancy checklist

Clause / Requirement

Compliance

Signature

4 General requirements
4.1 General

Praesideo is compliant.

4.1.1 If an optional function with requirements is

included in the VACIE, then all the corresponding

requirements shall be met (see Annex B).

The following optional functions, with requirements, are

included in Praesideo from version 3.3 upwards:

• Audible warning (7.3)

• Phased evacuation (7.5)

• Manual silencing of the voice alarm condition (7.6.2)

• Manual reset of the voice alarm condition (7.7.2)

• Output to fire alarm devices (7.8)

• Voice alarm condition output (7.9)

• Indication of faults related to the transmission path to

the CIE (8.3)

• Indication of fault related to voice alarm zones (8.4)

• Voice alarm manual control (10)

• Interface to external control device(s) (11)

• Emergency microphone(s) (12)

• Redundant power amplifiers (13.14)

The following optional functions with requirements are not

included in Praesideo:

• Delay(s) to entering the voice alarm condition (7.4)

• Disabled condition (9)

4.1.2 If functions other than those specified in this

European Standard are provided, they shall not

jeopardize compliance with any requirements of this

European Standard

Praesideo power amplifiers and basic amplifiers shall not be

configured to enter the power save mode when mains power

fails. Although this would save battery power, the amplifier

supervision and line/loudspeaker supervision is not active in

this mode, which is a necessity for systems operating in

accordance with EN54-16.

The Praesideo PC call station shall not be used as an

emergency call station in systems operating in accordance to

EN54-16. A PC does not comply with the requirements as set

forward by this standard.

4.2 Combined VACIE and CIE
When the VACIE and CIE are combined they may

share common indications, manual controls and

outputs (see Annex F). In this case, the following

shall apply:

a

single fault in the CIE shall not adversely

affect the mandatory functions of the VACIE;

b

indication(s) and manual control(s) of the

voice alarm condition shall be clearly

identifiable, with the exception of the optional

audible warning.

This requirement is not applicable. In Praesideo, the Voice

Alarm Control and Indicating Equipment (VACIE) is not

combined with a fire alarm Control and Indicating Equipment

(CIE).