8.6 Fault-warning condition output signal

The s.s.c.i.e. shall have an output to transmit the fault-

warning condition specified in 8.2. The output signal shall

be given if the s.s.c.i.e. is de-energized.

The Praesideo network controller provides two

predefined control outputs for audible and visual fault

indicators with fail-safe behavior. When de-energized,

the contacts of these control outputs are closed

(activated).

Clause / Requirement

Compliance

Signature

9 Disabled condition - Optional function
9.3 Indication of specific disablements
9.3.1
Each emergency loudspeaker zone shall be

indicated by means of separate light-emitting indicators

and/or an alphanumeric display. The indications shall

not be suppressed during the voice-alarm condition.

The optional disablement condition is not supported by

the Praesideo system.

9.3.3 The same light-emitting indicator may be used as

that for the indication of the corresponding fault, although

the indication shall be distinguishable. The same light-

emitting indicator and the same indication may be used

to indicate a disabled emergency loudspeaker zone and

an emergency loudspeaker zone under test.

The optional disablement condition is not supported by

the Praesideo system.

Clause / Requirement

Compliance

Signature

10 Test condition - Optional function

The optional test condition is not supported by the

Praesideo system.

Clause / Requirement

Compliance

Signature

11 Manual mode control - Optional function
11.1.2
In the manual mode, the receiving and display of

signals shall not be inhibited.

Praesideo does not inhibit the receiving and display of

signals in the manual mode.

11.1.3 In the manual mode, any phased evacuation

sequence shall be halted. Returning the system to

automatic mode shall reinstate the phased evacuation

sequence as if it had not been halted.

Praesideo will resume manually overruled calls after the

overruling call has finished, providing that the overruled

call was without live speech and had emergency priority.