8.6 Fault-warning condition output signal
The s.s.c.i.e. shall have an output to transmit the fault-
warning condition specified in 8.2. The output signal shall
be given if the s.s.c.i.e. is de-energized.
The Praesideo network controller provides two
predefined control outputs for audible and visual fault
indicators with fail-safe behavior. When de-energized,
the contacts of these control outputs are closed
(activated).
Clause / Requirement
Compliance
Signature
9 Disabled condition - Optional function
9.3 Indication of specific disablements
9.3.1 Each emergency loudspeaker zone shall be
indicated by means of separate light-emitting indicators
and/or an alphanumeric display. The indications shall
not be suppressed during the voice-alarm condition.
The optional disablement condition is not supported by
the Praesideo system.
9.3.3 The same light-emitting indicator may be used as
that for the indication of the corresponding fault, although
the indication shall be distinguishable. The same light-
emitting indicator and the same indication may be used
to indicate a disabled emergency loudspeaker zone and
an emergency loudspeaker zone under test.
The optional disablement condition is not supported by
the Praesideo system.
Clause / Requirement
Compliance
Signature
10 Test condition - Optional function
The optional test condition is not supported by the
Praesideo system.
Clause / Requirement
Compliance
Signature
11 Manual mode control - Optional function
11.1.2 In the manual mode, the receiving and display of
signals shall not be inhibited.
Praesideo does not inhibit the receiving and display of
signals in the manual mode.
11.1.3 In the manual mode, any phased evacuation
sequence shall be halted. Returning the system to
automatic mode shall reinstate the phased evacuation
sequence as if it had not been halted.
Praesideo will resume manually overruled calls after the
overruling call has finished, providing that the overruled
call was without live speech and had emergency priority.