Installation and User Instructions

Clause / Requirement

Compliance

Signature

10 Voice alarm manual control

(option with requirements)

10.1 General requirements

Praesideo is compliant.

The VACIE may have provision for manually activating

the voice alarm output condition. If a voice alarm output

control facility is provided the following shall apply:
a

a manual control which causes a voice alarm output

condition to be given shall only be accessible at

access level 2;

The Praesideo system can enter the voice alarm output

condition manually via control input contacts, the Open

Interface and call station (keypad) keys, by starting a call

with a high enough priority.

b

it shall be possible to activate each voice alarm zone

individually and/or in group(s) of voice alarm zones;

A voice alarm priority call can be manually activated in

one or more individual zones or zone groups. Zone

selection is possible via call station keypad keys or via

the Open Interface (e.g. using a PC Call Station for

graphical representation of zones with mouse or touch

screen selection).

Zones can also be added to and removed from a running

voice evacuation call using the ‘Start’ action, even from

other call stations or control inputs on other system

elements. A separate ‘Stop’ action is available to stop

such a call from any location.

c

the manual activation of a voice alarm zone shall not

prevent the mandatory indications and outputs to

other voice alarm zones.

Praesideo uses the concept of audio output assignment

to a dedicated zone. Because different zones use

different amplifiers, the activation of an additional voice

alarm zone will not affect other voice alarm zones.

Praesideo can be configured to abort lower priority calls

and BGM (Background Music) if a voice alarm state is

present.

The mandatory zone related indications are based on the

priority of the active call in the voice alarm zones. This

means that the lower priority boundary of the Zone status

indicator for each zone should be set to include all

priorities of possible alarm calls into that zone. Using

priority level 224 as lower boundary is a safe choice,

because then the Zone status indicator will cover all

possible alarm priorities (224-255).

10.2 Indication of the voice alarm zones in an

activated condition

Praesideo is compliant.

The indication for the voice alarm condition in the voice

alarm zone(s) associated with each manual control shall

be available without any manual action and shall not be

suppressed. This indication shall be by means of
a

a separate light emitting indicator (the General Voice

Alarm Output activated indicator), and

The voice alarm condition is indicated on the Praesideo

system by:

A red indicator on all call stations (the system

status LED).

A textual indicator on the network controller

display

An output contact configured as voice alarm

activated indicator (Emergency alarm indicator).

This output contact can be used to control the

General Voice Alarm Activated indicator.

b

a separate light emitting indicator and/or

alphanumeric display for each voice alarm zone and/

or an indication for group(s) of voice alarm zones.

The key-indicators on call station keypad kits (or regular

keypads) can be configured for ‘Zone status’, to show

that a (voice) alarm is active for a specific zone or group

of zones. The indication is based on the priority of the

active call in that zone, see 10.1. c.

NOTE - These indicators may not necessarily indicate

which emergency message is being broadcast in each

voice alarm zone.
10.3 Indication of the voice alarm zones in fault

condition

Praesideo is compliant.

The indication for the fault condition which would prevent

the generation and transmission of the voice alarm signal

to the voice alarm zone(s) associated with each manual

control shall be available without any manual action and

shall not be suppressed. This indication shall be by