5.3 Indication on alphanumeric displays

Praesideo is compliant.

Where an alphanumeric display is used to display

indications relating to different functional conditions

these may be displayed at the same time. However, for

each functional condition there shall be only one window,

in which all of the information relating to that functional

condition is grouped.

The alphanumeric display of the network controller

indicates the voice alarm condition by means of the

emergency menu. The display indicates the fault warning

condition by means of the faults menu.

If a fault occurs in the system, the faults menu is

displayed automatically. If the system enters the voice

alarm condition, the emergency menu is displayed

automatically. The emergency menu has precedence

over the faults menu.

The faults menu has a submenu for each individual fault.

The user can scroll through the individual faults.

The logging application delivered with the Praesideo

system offers a graphical user interface for viewing

events (Logging Viewer). The Logging Viewer has three

separate tab pages: Fault Events (shows events related

to the fault warning condition), Call Events and General

Events (shows events related to the voice alarm

condition).

5.4 Indication of the supply of power

Praesideo is compliant.

5.4.1 A visible indication shall be given by means of a

separate discrete light-emitting indicator while the VACIE

is supplied with power.

Each Praesideo system component either has a

dedicated power LED or a display with a backlight. For

components with a power LED, the LED is on when the

component is supplied with power. For components with

a display, the backlight of the display is on when the

component is supplied with power.

5.4.2 Where the VACIE is distributed in more than one

cabinet, an indication of supply of power to each

distributed cabinet shall be given at that point.

The Praesideo system can be distributed in more than

one cabinet, depending on the installation of the system.

Many system components can be mounted in a 19’’ rack.

Each cabinet will indicate supply of power independently

if the system is distributed in more than one cabinet.

5.5 Additional indications

Praesideo is compliant.

Where additional indications are provided, they shall be

clearly identifiable and shall not override the primary

indication of the VACIE.

For LEDs with multiple indication functions , all of the

additional indications are clearly identified (in the

Installation and User Instructions of the Praesideo

system); since the fault warning indication and the voice

alarm indication always have precedence over the

additional indications, the primary indications are not

overridden.

The LED indicator belonging to a key of the call station

keypad is used for status indications. The status

indications depend on the function which has been

assigned to the programmable key. The Installation and

User Instructions of the Praesideo system clearly

identifies the possible status indications. These status

indications do not override the primary indication of the

Praesideo system, since they are separate LEDs.

The display of the network controller offers a menu that

is also used for other indications than indication of the

voice alarm and/or fault warning condition. The

Installation and User Instructions of the Praesideo

system clearly identifies the other indications of the

menu. The other menus do not override the emergency

and faults menu; indication of the faults menu and

emergency menu has precedence (higher priority) over

indication of the other menus.

Clause / Requirement

Compliance

Signature

Advertising