Clause / Requirement

Compliance

Signature

11 Interface to external control device(s) (option with

the requirements)

The VACIE may have provision for interfacing to external

control device(s) such as standardized user interfaces

required by local regulations. In this case, the following

shall apply:

Praesideo is compliant.

a

the interface shall allow only access level 1 and 2

functions;

Using the Open Interface requires access level 2. The

Open Interface functionality is limited to call and BGM

(Background Music) control as well as acknowledge/

reset of fault and emergency states.

Praesideo provides control input contacts with

supervision and control output contacts for external

control devices, with extensive configurable functionality.

b

the mandatory functions of the VACIE shall not be

overridden;

The Praesideo system operates as an autonomous

system. All external activations are priority based to

control preference. By proper configuration system

behavior is tightly controlled and the mandatory functions

of the VACIE will not be overridden.

c

any short-circuit , interruption or earth fault in the

transmission path to the external device(s) shall
1

not prevent the mandatory function of the VACIE,

and

The Praesideo system operates as an autonomous

system, so its operation (functionality) is not affected by

loss of connection to an Open Interface client.

2

be indicated on the VACIE, at least by means of

the general fault warning indicator.

The connection to an Open Interface client is monitored

by means of a keep-alive mechanism; if the connection

is lost the general fault warning indicator is activated and

a specific fault is reported.

NOTE - The external control devices should comply with

available local or national standards.