Praesideo 4.0

en | 57

Bosch Security Systems B.V.

IUI-PRAESIDEO_4.0 | V1.0 | 2013.01

Installation and User Instructions

7.3 Audible warning (option with requirements)
An audible warning of the voice alarm condition might be

the same as that for the fault warning condition. If they

are different, the voice alarm condition warning shall

have priority.

Output contacts of the Praesideo system can be

configured in the site specific data as either Emergency

alarm buzzer or Fault alarm buzzer. A buzzer must

always be connected to the output contact to generate

the actual audible warning. A single buzzer can be used

as audible warning device for both the voice alarm

condition and the fault warning condition, by using a

parallel connection of the output contacts of the

Emergency alarm buzzer and the Fault alarm buzzer to

control the actual buzzer.

The Praesideo system does not offer priority handling for

the Emergency alarm buzzer (i.e. the Fault alarm buzzer

is not automatically silenced when the Emergency alarm

buzzer is activated).

7.4 Delays to entering the voice alarm condition

(option with requirements)

The VACIE may be provided with a facility to introduce a

delay before entering the voice alarm condition. In this

case:

Since the Praesideo system does not process the fire

sensors, this functionality is better handled by the device

managing the fire sensors (the CIE). The Praesideo

system itself does not implement this requirement.

a

the operation of the delay shall be selectable at

access level 3;

b

the operation of the delay shall be in increments not

exceeding 1 min up to a maximum of 10 min;

c

the delay to one output signal shall not affect the

delay to other outputs;

d

it shall be possible to override the delay by a manual

operation at access level 1;

e

there shall be provision to switch on and switch off

delays by means of a manual operation at access

level 2 (see Annex A for information on access

levels);

f

there may be provision to automatically switch on

and/or switch off delays by means of a

programmable timer which shall be configurable at

access level 3;

g

a separate discrete light emitting indicator and/or a

field on the alphanumeric display shall be visible

when a fire signal is received and the delay activated.

This indication shall be suppressed when the VACIE

enters the voice alarm condition.

7.5 Phased evacuation (option with requirements)

Praesideo is compliant.

The VACIE may have a provision to phase the warning

signals to the emergency loudspeaker zones. The facility

shall be configurable at access level 3. There may be

provision to switch on and switch off the phased

evacuation sequence by means of a manual operation at

access level 2 (see Annex A for information on access

levels).

Phased evacuation can be accomplished by phased

triggering of input contacts that start the same voice

alarm call in different zones. The device managing the

fire sensors (CIE) is responsible for the phased triggering

of the contacts. Voice alarm calls can also be started via

the Open Interface, where the device managing the fire

sensors (CIE) is responsible for the phased invocation of

the necessary Open Interface methods.

The input contacts must be configured at access level 3.

Using the Open Interface requires access level 2.

Praesideo also offers the possibility to start up to 5 calls

simultaneously from a single input contact or key,

configured as ‘Call activation key’ or ‘Start’, where

phasing can be implemented using accurately defined

periods of silence in the call macros, preceding the

actual tone or message. The installer shall configure the

calls correctly using these chimes/messages (at access

level 3) and use call station keypad keys to switch on

and off the chimes/messages (at access level 2).

7.6 Silencing of the voice alarm condition

Praesideo is compliant.

7.6.1 Silencing of the voice alarm condition from the

CIE

7.6.1.1 Where the voice alarm condition has been

triggered from the CIE, the VACIE shall respond

appropriately to a silence instruction from the CIE.

Voice alarm calls triggered from the CIE can also be

stopped from the CIE. To reset the voice alarm condition

an Acknowledge Emergency and Reset Emergency

action is required.

Clause / Requirement

Compliance

Signature