Praesideo 4.0

en | 75

Bosch Security Systems B.V.

IUI-PRAESIDEO_4.0 | V1.0 | 2013.01

Installation and User Instructions

a

all mandatory indications shall be visible at access

level 1 without prior manual intervention (e.g. the

need to open a door);

All indicators of the Praesideo system can be visible at

access level 1. The installer must ensure correct

implementation of this requirement.

b

manual controls at access level 1 shall be accessible

without special procedures;

Manual controls of the Praesideo system at access level

1 are accessible without special procedures.

c

indications and manual controls that are mandatory

at access level 1 shall also be accessible at access

level 2;

All Praesideo indications (LEDs, equipment connected to

output contacts, front panel display) and manual controls

(input contacts, call station keys, front panel menus) that

are accessible at access level 1 are also accessible at

access level 2.

d

entry to access level 2 shall be restricted by a special

procedure;

Entry to access level 2 is restricted by a special

procedure; refer to clause13.6, access level 2

description for details.

e

entry to access level 3 shall be restricted by a special

procedure, differing from that for access level 2;

Entry to access level 3 is restricted by a special

procedure, see clause13.6, access level 3 description for

details. Correct configuration and installation (physical

access control) will ensure that the special procedure

differs from that of access level 2. The system

administrator shall define users of type ‘user’ for access

level 2 and users of type ‘installer’ for access level 3. The

installer shall ensure that the physical access procedure

differs from that of the physical access procedure of

access level 2.

f

the entry to access level 4 shall be restricted by

special means which are not part of the VACIE.

Entry to access level 4 is restricted by means of having

to use the File Transfer Application (FTA), see

clause13.6, access level 4 description for details. This

FTA is only used for access level 4 functions and is

therefore not part of the daily operation/configuration of

the Praesideo system.

NOTE - Further access levels are permitted provided that

they are distinct from the access levels described in this

standard.
13.7 Indications by means of light-emitting

indicators

Praesideo is compliant.

13.7.1 Mandatory indications from light emitting

indicators shall be visible in an ambient light intensity up

to 500 lux, at any angle up to 22.5° from a line through

the indicator perpendicular to its mounting surface

at 3 m distance for the general indications of

functional condition,

at 3 m distance for the indication of the supply of

power, and

at 0.8 m distance for other indications.

All of the light emitting indicators of the Praesideo

system fulfill this requirement. When external light

emitting indicators are installed, such as LEDs

connected to a call station kit or call station keypad kit, or

light emitting indicators connected to output contacts, the

installer shall use indicators that fulfill this requirement.

13.7.2 If flashing indications are used, both the on

period and the off period shall be greater than or equal to

0.25 s, and the frequencies of flash shall not be less than

1 Hz for voice alarm indications, and

0.2 Hz for fault indications.

The voice alarm indication does not flash; it is steady on

both call stations and on output contacts.

The fault indication on a call station flashes with a

frequency of 2 Hz (on and off period of 0.25 s) when

there is a fault in the system or is steady on when there

is a fault in the call station itself. The fault indication on

output contacts is always steady on.

13.7.3 If the same light emitting indicators are used for

the indication of specific faults and disablements, fault

indications shall be flashing and disablement indications

shall be steady.

Disablement indication is not available in the Praesideo

system since Praesideo does not support the optional

disablement condition.

13.8 Indications on alphanumeric displays

Praesideo is compliant.

13.8.1 If an alphanumeric display consists of elements

or segments, the failure of one of these shall not affect

the interpretation of the displayed information.

Praesideo system elements that have an alphanumeric

display all have a dot matrix LCD. If a single dot of such

a display fails the interpretation of the displayed

information is not affected.

13.8.2 If an alphanumeric display is used to display

mandatory indications, it shall be clear and

unambiguous.

The display of the network controller is used to display

mandatory indications. Indication of the voice alarm

condition is by means of the text ‘Emergency’ and the

name of the key that activated the voice alarm condition.

Indication of the fault warning condition is by means of

the text ‘Faults’ and an indication of the number of active

faults in the system. Individual faults with details are

shown in a menu structure.

Clause / Requirement

Compliance

Signature