Инструкция по эксплуатации Bosch Praesideo 4.0

Страница 50

Advertising
background image

Praesideo 4.0

en | 60

Bosch Security Systems B.V.

IUI-PRAESIDEO_4.0 | V1.0 | 2013.01

Installation and User Instructions

Clause / Requirement

Compliance

Signature

8 Fault warning condition
8.1 Reception and processing of fault signals

Praesideo is compliant.

8.1.1 The VACIE shall enter the fault warning condition

when signals are received which, after any necessary

processing, are interpreted as a fault.

When the Praesideo system receives a supervision fault

signal (i.e. detects a fault in the system), the fault warning

condition is entered until this state is explicitly reset.

8.1.2 The VACIE shall be capable of simultaneously

recognizing all of the faults specified in 8.2 and, if

provided, in 8.3 unless this is prevented by:

the presence of an alarm output signal on the same

voice alarm zone, and/or

All Praesideo system faults are handled (acknowledged

and reset) individually. Also, the Praesideo system is

capable of recognizing all of its system faults

simultaneously. The Praesideo system is able to

recognize faults in a voice alarm zone even when there

is an alarm output signal on the zone.

the disablement of the corresponding voice alarm

zone or function.

Optional disablement of voice alarm zones or functions is

not implemented in Praesideo.

8.1.3 The VACIE shall enter the fault warning condition

within 100 s of the occurrence of any fault, or the reception

of a fault signal or within another time as specified in this

European Standard or in other parts of EN 54.

The Praesideo system recognizes and reports all faults

within 100 seconds.

8.2 Indication of faults in specified functions

Praesideo is compliant.

8.2.1 The presence of faults in specified functions shall

be indicated on the VACIE without prior manual

intervention. The fault warning condition is established

when the following are present:
a

a visible indication by means of a separate light

emitting indicator (the general fault warning

indicator);

The Praesideo system provides a visible indication when it

is in the fault warning condition via the fault LED of the call

stations, output contacts, key indicators of call station

keys, the fixed fault output contact of the network controller

and the front panel menu of the network controller.

The installer must mount a yellow (flash) light to indicate

the fault warning condition, clearly visible from the front

side of the rack, behind the glass door of the rack.

b

a visible indication for each recognised fault as

specified in 8.2.3, 8.2.4, 8.3 (if provided), 8.4 (if

provided) and 8.5 and

The Praesideo system offers two ways of visual

indication of individual faults: via the front panel menu of

the network controller and via the Praesideo logging

application.

c

an audible indication, as specified in 8.6.

The Praesideo system provides an audible fault

indication when it is in the fault warning condition via

output contacts and the fixed audible fault output contact

of the network controller.

8.2.2 If the indication is on an alphanumeric display, which

cannot simultaneously indicate all of the faults because of

its limited capacity, at least the following shall apply:
a

the presence of fault indications which have been

suppressed shall be indicated;

The network controller alphanumeric display is used to

indicate the fault warning condition and all individual faults.

The normal display information of the network controller

is automatically overruled when there are faults present,

i.e. when the system enters the fault warning state. The

display of the network controller indicates the number of

faults present.

b

suppressed fault indications shall be capable of

being displayed by means of a manual operation at

access level 1 or 2 which interrogates only fault

indications.

The individual faults are presented in the ‘Faults’ menu

of the front panel menu of the network controller. Manual

operation is needed to display and navigate through the

individual faults. Each individual fault is shown in a

submenu of the ‘Faults’ menu.

8.2.3 The following faults shall be indicated by means of

separate light emitting indicators and/or an alphanumeric

display:

Faults of the supervised items are detected and reported

through the general fault warning indication. Additionally

all faults are reported individually as well and can be

inspected using the network controller front panel menu

and the logging application.

a

an indication at least common to any power supply

fault resulting from:

The mains and backup power of all Praesideo system

elements are supervised individually.

1

a short circuit or an interruption in a transmission

path to a power supply (item L of Figure 1 of

EN 54-1), where the power supply is contained in

a different cabinet from that of the VACIE, and

2

the power supply faults as specified in EN 54-4;

Advertising