Excluded clauses

Clause / Requirement

Compliance

Signature

EN54-16, clause 12.1 Emergency microphone -

option with requirements.
c Where a pre-announcement attention drawing signal

is provided, an indicator adjacent to the microphone

shall show when the signal has finished and live

speech can commence.

This clause is not part of ISO7240-16.

Clause / Requirement

Compliance

Signature

EN54-16, clause 13.4.1 Electrical and other design

requirements

The processing of signals shall give the highest priority

to the voice alarm condition.

This clause is not part of ISO7240-16.

EN54-16, clause 13.13 Message store(s)

Pre-recorded messages shall be stored in non-volatile

memory that retains the messages when all power

sources are removed.

NOTE The use of tapes or magnetic or optical data disks

for the storage of emergency messages is not

acceptable at the time of drafting this European Standard

(see Annex C)

The NOTE is not part of ISO7240-16.