Excluded clauses – Инструкция по эксплуатации Bosch Praesideo 4.0
Страница 87
Praesideo 4.0
en | 97
Bosch Security Systems B.V.
IUI-PRAESIDEO_4.0 | V1.0 | 2013.01
Installation and User Instructions
Excluded clauses
Clause / Requirement
Compliance
Signature
EN54-16, clause 12.1 Emergency microphone -
option with requirements.
c Where a pre-announcement attention drawing signal
is provided, an indicator adjacent to the microphone
shall show when the signal has finished and live
speech can commence.
This clause is not part of ISO7240-16.
Clause / Requirement
Compliance
Signature
EN54-16, clause 13.4.1 Electrical and other design
requirements
The processing of signals shall give the highest priority
to the voice alarm condition.
This clause is not part of ISO7240-16.
EN54-16, clause 13.13 Message store(s)
Pre-recorded messages shall be stored in non-volatile
memory that retains the messages when all power
sources are removed.
NOTE The use of tapes or magnetic or optical data disks
for the storage of emergency messages is not
acceptable at the time of drafting this European Standard
(see Annex C)
The NOTE is not part of ISO7240-16.