Installation and User Instructions

b

an indication at least common to any earth fault of

less than 50 k

Ω is capable of affecting a mandatory

function, and which is not otherwise indicated as a

fault of a supervised function;

All 100V lines of the Praesideo system can be

supervised individually for earth faults (i.e. connections

to earth with a leakage resistance of less than 50 k).

c

an indication of the rupture of any fuse within the

VACIE, or the operation of any protective device

within the VACIE which is capable of affecting a

mandatory function in the fire alarm condition;

Every rupture of a fuse or the operation of a protected

device that affects a mandatory function will result in a

fault since the mandatory functions are supervised. The

reported fault is as close to the located defect as

possible. E.g. a mains related fault is reported as a

mains fault and an amplifier defect is reported as defect

for that amplifier channel.

d

an indication of any short circuit or interruption, at

least common to all transmission paths between

parts of the VACIE contained in more than one

cabinet, which is capable of affecting a mandatory

function and which is not otherwise indicated as a

fault of a supervised function.

All network based transmission paths of the Praesideo

system are supervised using a keep-alive mechanism.

The CobraNet transmission path of the Praesideo

system is supervised by means of clock availability.

When the Praesideo system is used in a redundant loop

configuration, the loss of the redundant path is reported.

All control input contacts of the Praesideo system can be

supervised for shorts and interruptions.

Analog audio connections to external parties can be

supervised by pilot tone supervision.

The analog fail safe bypass input of the Praesideo multi

channel interface can be supervised by pilot tone

supervision.

These indications may be suppressed during the fire

alarm condition.

Praesideo fault indicators are not suppressed. There are

separate indicators for fault and voice alarm conditions.

The only exception is that the automatic indication of the

voice alarm condition has precedence over the

automatic indication of the number of present faults on

the display of the network controller.

8.2.4 The following faults shall be indicated at least by

means of the general fault warning indicator:
a

any short-circuit or interruption in a voice alarm

transmission path between parts of the VACIE

contained in more than one cabinet even where the

fault does not affect a mandatory function;

All network based transmission paths of the Praesideo

system are supervised using a keep-alive mechanism.

The CobraNet transmission path of the Praesideo

system is supervised by means of clock availability.

When the Praesideo system is used in a redundant loop

configuration, the loss of the redundant path is reported.

All control input contacts of the Praesideo system can be

supervised for shorts and interruptions.

Analog audio connections to external parties can be

supervised by pilot tone supervision.

The analog fail safe bypass input of the Praesideo multi

channel interface can be supervised by pilot tone

supervision.

b

any short-circuit or interruption in the voice alarm

transmission path to the emergency microphone

capsule, if provided;

The capsule of the Praesideo (emergency) call station

microphone can be supervised for both short-circuit and

interruption. This is configurable. Also the microphone

inputs on the power amplifiers supervise the connected

microphone.

c

any short-circuit or interruption in the voice alarm

transmission path between the VACIE and

loudspeakers even where the fault does not affect

the operation of loudspeakers.

The loudspeaker lines of the Praesideo system can be

supervised using a master-slave communication system

that uses the actual loudspeaker wiring for polling. The

communication is inaudible and not affected by audio

signals present.

Praesideo offers two options: single loudspeaker line

supervision (master-slave) and multiple loudspeaker line

supervision (master-multiple slaves) that detect short-

circuits and interruption of the loudspeaker lines.

The installer shall only use the 100 V outputs of the

Praesideo amplifiers.

Clause / Requirement

Compliance

Signature