Installation and User Instructions

a

a separate light emitting indicator (the general fault

indicator), and

The Praesideo system provides a visual indication when

it is in the fault warning condition via the fault LED of the

call stations, control output contacts, key indicators of

call station keys, the fixed fault output contact of the

network controller and the front panel menu of the

network controller.

All Praesideo call stations have a specific fault indicator,

the power/fault LED, which is blinking yellow for a

system fault and steady yellow when there is a fault in

the call station or the Praesideo network is not

operational. The power/fault LED is green when there is

no fault in the system.

Control output contacts can be configured as ‘Fault

alarm indicator’. A visual indicator (e.g. a lamp) can be

connected to the output contact. The output contact is

activated when the system enters the fault warning

condition. The output contact is de-activated when the

system leaves the fault warning condition, i.e. when all

faults are reset.

Call station keypad keys can be configured to the action

‘Reset fault’ or ‘Ack and reset fault’. The key indicator of

such a key will now light up when the system enters the

fault warning condition. The key indicator is turned off

when the system leaves the fault warning condition.

Output contact 5 of the network controller is the fixed

Fault alarm indicator output. Other control outputs can be

configured for the same function. If a visual indicator is

connected to this output contact it can be used as the

general fault warning indicator.

The network controller displays the number of present

faults. This fault indication overrules the normal display

information.

b

an indication for each voice alarm zone and/or an

indication for defined group(s) of zones.

The key-indicators on call station keypad kits (or regular

keypads) can be configured for ‘Zone status’, to show

that a (voice) alarm is active for a specific zone or group

of zones. A second key indicator for this ‘Zone status’

function shows whether the zone is in fault state. The

zone fault state indicator is the visual representation of

the collection of all faults that may affect the voice alarm

in that zone.

The zone fault state is also available on PC call stations,

connected to the Open Interface. Here the zone-icons on

the screen get a fault warning indication in case of a

zone fault.

More in general: all faults are visible on the front panel

menu of the Network Controller and via the Praesideo

logging application.

By configuring sensible names for the zones and

amplifier outputs contributing to these zones, fault

indications become clear and easy to understand. For

instance, a zone can have the name 'Floor_3' and output

4 of amplifier 'A6', contributing to that zone may have the

name 'Floor_3 A6_4'. A short circuit on that amplifier

output will then be shown including its name 'Floor_3

A6_4' and it will be clear that the sound on Floor_3 will

be affected.

10.4 Indication of the voice alarm zones in

disablement condition

The indication for the disablement condition in the voice

alarm zone(s) associated with each manual control shall

be available without any manual action and shall not be

suppressed. This indication shall be by

Praesideo does not support the optional disablement

condition.

a

a separate light emitting indicator (the general

disablement indicator), and

b

an indication for each voice alarm zone and/or an

indication for defined group(s) of zones.