Praesideo 4.0

en | 53

Bosch Security Systems B.V.

IUI-PRAESIDEO_4.0 | V1.0 | 2013.01

Installation and User Instructions

Clause / Requirement

Compliance

Signature

5 General requirements for indications
5.1 Display and functional conditions

Praesideo is compliant.

5.1.1 The VACIE shall be capable of unambiguously

indicating the following functional conditions, as

described in Clauses 6 to 9:

• quiescent

condition;

• voice alarm condition;

• fault warning condition;

• disablement condition (option with requirements)

See Clauses 6 to 9.

5.1.2 The VACIE shall be capable of being

simultaneously in any combination of the following

functional conditions on different voice alarm zones:

The Praesideo system is capable of being

simultaneously in the voice alarm condition and in the

fault warning condition.

voice alarm condition;

The voice alarm condition is indicated per system on

each call station (system status LED) and on the display

of the network controller (emergency menu). This system

wide indication can be combined with the indication of

the fault warning condition: each call station uses a

different LED (power/fault LED) for indication of the fault

warning condition; therefore both conditions can be

indicated simultaneously. The display of the network

controller can indicate both the voice alarm condition and

the fault warning condition (note that it will only show one

condition automatically, the voice alarm condition has

precedence; the user is able to see the fault warning

condition by navigating through the menu if both

conditions apply to the system simultaneously).

To indicate the voice alarm condition per zone, the

installer shall use a call station keypad kit with correctly

connected red LEDs (see clause 13.9.1) with

configuration of the ‘Zone status’.

fault warning condition;

The fault warning condition is indicated per system on

each call station (power/fault LED) and on the display of

the network controller (faults menu). This system wide

indication can be combined with the indication of the

voice alarm condition: each call station uses a different

LED (system status LED) for indication of the voice

alarm condition; therefore both conditions can be

indicated simultaneously. The display of the network

controller can indicate both the voice alarm condition and

the fault warning condition (note that it will only show one

condition automatically, the voice alarm condition has

precedence; the user is able to see the fault warning

condition by navigating through the menu if the system is

in both conditions simultaneously).

The installer must configure zone names in a way that

the zone name is visible in the fault logging and network

controller display (see clause 8.2.7 for details). In this

way faults are indicated per zone.

disablement condition (option with requirements).

The optional disablement condition is not implemented in

Praesideo.

5.2 Indication display

Praesideo is compliant.

All mandatory indications shall be clearly identifiable,

except where otherwise specified in this European

Standard.

The Praesideo system uses the following color coding for

indications throughout the system:

• Green: system ok

• Red: system/zone in voice alarm condition

• Yellow: system in fault warning condition