Changed clauses – Инструкция по эксплуатации Bosch Praesideo 4.0
Страница 84
Praesideo 4.0
en | 94
Bosch Security Systems B.V.
IUI-PRAESIDEO_4.0 | V1.0 | 2013.01
Installation and User Instructions
Changed clauses
Clause / Requirement
Compliance
Signature
17 Tests
All tests as asked for in the clauses of section 17 have
been carried out by an accredited certification body for
ISO7240-16 compliancy.
The Praesideo system has been found compliant to
ISO7240-16 and received a certification of compliancy.
Clause / Requirement
Compliance
Signature
18 Test report
The tester must take care of documenting the testing
programme and the results of the tests in a test report
that at least contains the information as listed in clause
18.
Clause / Requirement
Compliance
Signature
4.3 Power supply
Power-supply equipment shall comply with the
requirements of ISO 7240-4 and may be internal or
external to the s.s.c.i.e. cabinet.
The power supply may be shared with that of the
emergency detection system.
The installer must use power supplies and battery
charging equipment in accordance with ISO7240-4, with
separate wiring for mains (230Vac) and battery backup
(48Vdc) from the power supply to the Praesideo system.
The power supply equipment must be installed in a
separate cabinet, not shared with the Praesideo system,
unless the combination of the actual power supply
equipment and Praesideo system elements in the same
cabinet has been certified.
The content of the ISO7240-16 certification is subject to
change. The most recent version of this certificate can
be found on www.boschsecurity.com.
The network controller and all amplifiers are supplied
with a mains supply and DC backup supply (48V) input.
Switch over between the both takes place automatically,
without any interruption or status change other than the
power supply related indications.
The installer must ensure that the output voltages of the
power supply equipment do not exceed the
specifications of the mains and battery inputs of the
connected Praesideo equipment.
Clause / Requirement
Compliance
Signature
8 Fault-warning condition
8.5 Reset of fault indications
8.5.2 Following the completion of the reset process, the
indication of the correct functional conditions
corresponding to any received signals shall either remain
or be re-established within 100 s.
If any individual fault is reset while it is not actually
resolved in the system, the Praesideo system will report
the fault again within 100 seconds. If all faults are reset
in one action, all individual faults that are not actually
resolved in the system are reported again within 100
seconds.
Clause / Requirement
Compliance
Signature
9 Disabled condition - Optional function
9.3 Indication of specific disablements
9.3.4 If the indication is on an alphanumeric display that
cannot simultaneously indicate all of the disablements
because of its limited capacity, at least the following shall
apply.
Praesideo does not support the optional function
disabled condition. See 9.
b Suppressed disablement indications shall be capable
of being displayed, independently of other
indications, by means of a manual operation at
access level 1 or 2, which interrogates only the
disablement indications.