7.6.1.2 The silencing procedure may allow for the

completion of messages in the process of being

broadcast.

A voice alarm call that is stopped while not being finished

will still complete the running message. Praesideo also

offers the possibility to abort running calls in which case

a running message will not be completed.

Praesideo allows configuration of two different voice

alarm reset actions: one that can only reset a voice alarm

condition when all running alarm calls have been

finished, and one that aborts all still running alarm calls.

7.6.2 Manual silencing of the voice alarm condition

(option with requirements)

7.6.2.1 It shall be possible to manually silence the voice

alarm message from the VACIE at access level 2.

Praesideo offers the possibility to stop voice alarm calls

by de-activating the contact or key that started the call.

Using the ‘Stop’ action, also calls started by a ‘Start’

action from a different key or contact can be aborted.

7.6.2.2 Following silencing, it shall be possible to

re-activate the voice alarm message at access level 2.

Voice alarm call can be re-activated by starting that call

again from a contact, a key or the Open Interface.

7.7 Reset of the voice alarm condition

Praesideo is compliant.

7.7.1 Reset of the voice alarm condition from the CIE
Where the voice alarm condition has been triggered from

the CIE, the VACIE shall respond appropriately to a reset

instruction from the CIE.

See 7.6.1.1.

7.7.2 Manual reset of the voice alarm condition

(option with requirements)

7.7.2.1 It shall be possible to reset the voice alarm

condition from the VACIE at access level 2 by means of a

separate manual control. This control shall be used only

for reset and may be the same as that used for reset

from the fault warning condition.

To reset the voice alarm condition an Acknowledge

Emergency and Reset Emergency action is required.

Praesideo allows configuration of two different voice

alarm reset (Emergency Reset) actions: one that can

only reset a voice alarm condition when all running alarm

calls have been finished, and one that aborts all still

running alarm calls.

7.7.2.2 Following a reset operation, the indication of the

correct functional condition corresponding to any

received signals shall either remain or be re-established

within 20 s.

After a reset operation, the Praesideo system will

immediately indicate the functional condition it is

currently in. It will also immediately respond to received

signals that will bring it into another functional condition.

7.8 Output to fire alarm devices

(option with requirements)

Praesideo is compliant.

In addition to the voice alarm outputs the VACIE may

have provision for the automatic transmission of fire

alarm signals to fire alarm devices such as beacons and

vibrating devices. In this case, the following shall apply:
a

it shall be possible to de-activate the fire alarm

devices at access level 2;

Fire alarm devices can be activated from control outputs

that are assigned to zones, which themselves are

assigned to calls. If a call is started via a ‘Start’ action,

the zone with the associated control output can be added

to that call by means of an additional ‘Start’ action for the

same call macro. Then it can be de-activated also by de-

activating that ‘Start’ action, or using an associated 'Stop'

action.

b

following de-activation, it shall be possible to

re-activate the fire alarm devices at access level 2;

Re-activating the ‘Start’ action, after being de-activated,

will add the zone with the associated control output to the

call again. The control output will activate the alarm

device again.

c

the fire alarm devices shall not be de-activated

automatically;

Using a 'Start' action with Momentary behavior, the fire

alarm devices will run in parallel with the original call to

which they are assigned. In case the fire alarm devices

should continue when the original call is stopped, then its

'Start' action should use Single-shot behavior to remain

activated until a 'Stop' action occurs.

d

it shall be possible to configure the VACIE at access

level 3 to automatically reactivate the fire alarm

devices if an alarm is reported in an other zone.

Praesideo allows multiple calls to be started

simultaneously from the same key or contact. An alarm

in an other zone that triggers the Praesideo system for

action in that zone may also start a call that activates or

re-activates the alarm device that is associated to a

different zone.

Clause / Requirement

Compliance

Signature