Installation and User Instructions

13.4 Electrical and other design requirements

Praesideo is compliant.

13.4.1 The processing of signals shall give the highest

priority to the voice alarm condition.

Calls within the Praesideo system have a configured

priority. In case of conflicting requirements, system

resources are assigned to the calls in order of priority.

Voice alarm call must be configured with a high priority

(priority 224-255). Many secondary functions of the

system can be configured to stop or pause in case calls

above a certain configured priority are present; this

includes calls below a certain configured priority.

13.4.2 Transitions between the main and the standby

power sources shall not change any indications and/or

the state of any outputs, except those relating to the

power supplies.

Transition between the main and standby power sources

does not change any of the indications and/or state of

any outputs of the Praesideo system, except for the fault

warning indication (global and individual) in order to

report the failure of a power source.

13.4.3 If the VACIE has provision for disconnecting or

adjusting the main or the standby power source, this

shall only be possible at access level 3 or 4.

The Praesideo system elements that have a mains and

backup power supply offer connectors for the main and

standby power source, a rear-mounted voltage selector

switch and on/off switch. The installer must ensure that

these items are only accessible at access level 3 or 4.

13.5 Integrity of transmission paths

Praesideo is compliant.

13.5.1 A fault in any voice alarm transmission path

between the VACIE and other components of the voice

alarm system shall not affect the correct functioning of

the VACIE or of any other voice alarm transmission path.

The Praesideo system has the following voice alarm

transmission paths between itself and other parts of the

voice alarm system:

transmission path between CIE and Praesideo

system via input contact or Open Interface;

transmission path between Praesideo system

and the loudspeaker(s).

If there is a fault in the transmission path between the

CIE and an input contact of the Praesideo system, the

configured action of the input contact will not be

automatically activated or de-activated. The correct

functioning of the Praesideo system or of any other voice

alarm transmission path is therefore not affected. The

fault will just be reported.

If there is a fault in the transmission path between the

CIE and the Ethernet connection of the network

controller of the Praesideo system (connection via Open

Interface), methods can no longer be invoked by the CIE

and no events can be notified to the CIE. However the

fault will not affect the correct functioning of the

Praesideo system or any other voice alarm transmission

path. The fault will just be reported.

If there is a fault in the transmission path between the

Praesideo system, i.e. the amplifier outputs and the

loudspeaker(s), the loudspeaker(s) will not be able to

produce the intended audio signal. However the fault will

not affect the correct functioning of the Praesideo system

or any other voice alarm transmission path. The fault will

just be reported.

13.5.2 A short circuit or an interruption in the

transmission path to the loudspeaker(s) shall not affect

more than one voice alarm zone for longer than 100 s

following the occurrence of the fault.

Each audio output of the Praesideo system can only be

assigned to one voice alarm zone by means of

configuration. The IUI specifies this clearly. Due to this, a

short circuit or interruption in the transmission path to the

loudspeaker(s) only affects the voice alarm zone it was

assigned to.

Clause / Requirement

Compliance

Signature