IUI-PRAESIDEO_4.0 | V1.0 | 2013.01

Installation and User Instructions

8.6.2 The audible indication shall be silenced

automatically if the VACIE is automatically reset from the

fault warning condition.

Since the Praesideo system does not offer automatic

reset from the fault warning condition this requirement

does not need to be implemented.

8.6.3 If previously silenced, the audible indication shall

resound for each newly recognized fault.

After the audible indication has been silenced (by

acknowledging all faults) the Praesideo system will

resound the indication upon occurrence of a new fault or

reoccurrence of a previously resolved fault.

8.7 Reset of fault indications

Praesideo is compliant.

8.7.1 Indications of faults as required in 8.2 shall be

capable of being reset
a

automatically when faults are no longer recognized,

and/or

The Praesideo system does not offer automatic reset of

faults

b

by a manual operation at access level 2.

Faults can be manually reset by acknowledging and

resetting them individually or all in one action.

Acknowledging and/or resetting faults individually can be

done via the front panel menu of the Network Controller

and via the Open Interface. Acknowledging and/or

resetting all faults in one action can be done via the front

panel menu of the network controller, control input

contacts, call station keys or the Open Interface.

8.7.2 Following reset as specified in 8.7.1, the indication

of the correct functional conditions corresponding to any

received signals shall either remain or be re-established

within 20 s.

If any individual fault is reset while it is not actually

resolved in the system, the Praesideo system will report

the fault again within 20 seconds. If all faults are reset in

one action, all individual faults that are not actually

resolved in the system are reported again within 20

seconds.

8.8 Transmission of the fault warning condition

Praesideo is compliant.

The VACIE shall have provision for transmitting, by

means of at least general fault signal, all faults specified

in 8. This fault signal shall also be given if the VACIE is

de-energized.

Output contact 5 of the Praesideo network controller is

the fixed Fault alarm indicator output. This relay output

contact indicates no fault when open (energized) and

indicates a fault when closed (de-energized). If the

Praesideo system is de-energized this output contact is

closed, therefore the fault signal will also be given.