Installation and User Instructions

Clause / Requirement

Compliance

Signature

14 Design requirements
14.2 Documentation
14.2.1
The manufacturer shall prepare installation and

user documentation, which shall be submitted to the

testing authority together with the s.s.c.i.e. This shall

comprise at least the following:
b technical specifications of the inputs and outputs of

the s.s.c.i.e., sufficient to permit an assessment of the

mechanical, electrical, and software compatibility with

other components of the system (e.g. as described in

ISO 7240-1), including where relevant

3 the maximum number of alarm inputs from an

emergency detection system

The inputs and outputs for audio and control are

described in the IUI, including the technical data, system

functions, configuration instructions, compliancy to

standards. This includes the information as requested in

14.2.1 b 3.

c installation information, including

The IUI contains all information as requested in 14.2.1 c1-5.

1 the suitability for use in various environments,
2 how the requirements of 14.3.3 and 14.5.3 can be

met if the s.s.c.i.e. is contained in more than one

cabinet,

3 how the requirements of 14.3.3 and 14.5.4 can be

met if the s.s.c.i.e is designed to be used with

power-supply equipment contained in a separate

cabinet,

4 mounting instructions, and
5 instructions for connecting the inputs and outputs.

14.3.3 The s.s.c.i.e. may be housed in more than one

cabinet. If the documentation shows that the cabinets

may be installed in locations distributed within a site,

then all of the mandatory manual controls and indicators

shall be on one cabinet or on cabinets declared to be

suitable only for mounting adjacent to each other.

NOTE For the purposes of 14.3.3, adjacent cabinets are

those that are mounted in physical contact with each other.

In case Praesideo is installed in multiple cabinets in

locations distributed within a site, the installer must

arrange that all mandatory manual controls and

indicators are on the same location, either by installing

them on a single cabinet or on adjacent cabinets that are

mounted in physical contact with each other.

14.8 Indications on alphanumeric displays
14.8.2
Alphanumeric displays used for mandatory

indications shall have at least one clearly distinguishable

window, consisting of at least two clearly identifiable

fields.

The display of the network controller is used to display

mandatory indications. It consists of two separate lines of

text, each representing a specific field, clearly

identifiable.

14.8.3 If not included in the displayed information, the

purpose of each field shall be clearly labelled.

Indication of the voice alarm condition is by means of the

text 'Emergency' and the name of the key that activated the

voice alarm condition. Indication of the fault warning

condition is by means of the text 'Faults' and an indication of

the number of active faults in the system. Individual faults

with details are shown in a menu structure.

14.8.4 Where roman characters are used, a field shall be

capable of containing at least the following:
a at least 16 characters where the display of a

functional condition uses a cross-reference to other

information to identify the location;

The display of the network controller consists of two lines

with 16 characters each. It uses a menu with rotary knob

navigation to select additional detailed information about

functional conditions.

b at least 40 characters where the display is intended

to include the complete information on the location of

a functional condition.

Not applicable, see 14.8.4.a.

14.8.5 Where other characters are used, a field shall be

capable of containing at least the following:

Not applicable, see 14.8.4.

a at least 4 characters where the display of a functional

condition uses a cross-reference to other information

to identify the location;

b at least 8 characters where the display is intended to

include the complete information on the location of a

functional condition.

14.9 Colours of indications
14.9.1
The colours of the general and specific indications

from light-emitting indicators shall be as follows:
b yellow for indications of

3 emergency loudspeaker zones in the test state.

The test condition is an optional function and is not

supported by Praesideo. See 10.