Installation and User Instructions

Clause / Requirement

Compliance

Signature

17 Tests

All tests as asked for in the clauses of section 17 have

been carried out by an accredited certification body for

ISO7240-16 compliancy.

The Praesideo system has been found compliant to

ISO7240-16 and received a certification of compliancy.

17.1 General
17.1.5 Mounting arrangements

The specimen shall be mounted by its normal means of

attachment in accordance with the manufacturer's

instructions. If these instructions describe more than one

method of mounting, then the method considered to be

the least favourable shall be chosen for each test.
17.2 Functional test
17.2.2.4 Test schedule - Disabled condition

Where a disablement function is provided, disable and

restore at least two emergency loudspeaker zones

(unless only one zone is provided).

Check that the operation of the disablement controls

result in the correct indication on the s.s.c.i.e., that only

the relevant parts of the system are disabled and that, on

restoration of the disablements, the function is restored.

Praesideo does not support the optional function

disabled condition. See 9.

17.3 Test schedule
17.3.4 Test for three specimens

If three specimens are supplied for environmental

testing, then one test specimen is subjected to all the

operational tests, which may be carried out in any order.

The second specimen shall be subjected to one of the

endurance tests, and the third specimen shall be

subjected to the other endurance test. Before and after

each environmental test, a functional test shall be carried

out.

For the first specimen, the functional test after one

environmental test may be taken as the functional test

before the next environmental test.
17.4 Output power
17.4.2.2 State of the specimen during conditioning

Mount the specimen as specified in 17.1.5 and connect it

to suitable power-supply, monitoring and loading

equipment, as specified in 17.1.3.

The specimen shall be in the quiescent condition.
17.4.2.3 Conditioning

Apply the following severity of conditioning:

• temperature: 40 °C ± 2 °C.

Precondition the specimen at the conditioning

temperature (40 °C ± 2 °C) until temperature stability has

been reached to prevent the formation of water droplets

on the specimen.

Terminate the s.s.c.i.e. output(s) with the minimum

resistive and maximum capacitive load representing the

loudspeaker lines and loudspeakers.

Adjust the power-supply equipment output to the nominal

primary power source level.

Apply the 1 kHz sinusoidal signal to the input of the

specimen and adjust the gain of the system until the

rated r.m.s. output power is achieved.

Maintain this gain for 1 min.
17.4.2.5 Final measurements

After 1 h recovery time at standard atmospheric

conditions, measure the frequency response of the

specimen in accordance with 17.6 or 17.7, as applicable.