Инструкция по эксплуатации Bosch Praesideo 4.0

Страница 52

Advertising
background image

Praesideo 4.0

en | 62

Bosch Security Systems B.V.

IUI-PRAESIDEO_4.0 | V1.0 | 2013.01

Installation and User Instructions

d

any short-circuit or interruption in the transmission

path between the VACIE and fire alarm devices when

used (see 7.8).

The Praesideo system does not offer this functionality

directly: control inputs are supervised, but control

outputs are just voltage free relay contacts. The installer

must create a feedback signal (corresponding to the

transmission path status between the Praesideo system

and the fire alarm device) to a supervised input contact

of the Praesideo system.

e

failure of any power amplifier.

All Praesideo power amplifiers are supervised for

overload, overheating, short-circuit, ground short and

amplifier defect.

8.3 Indication of faults related to the transmission path to

the CIE (option with requirements)
The VACIE may have provision for an indication of faults

related to the transmission path to the CIE. In this case,

the short-circuit or interruption of the transmission path to

the CIE shall be indicated by means of a separate light

emitting indicator and/or an alphanumeric display.

All input contacts of the Praesideo system can be

supervised for short and interruption.

Open Interface connections are supervised through

keep-alive messaging.

Faults related to the transmission path to the CIE are

therefore individually reported and can be inspected

using the front panel menu of the network controller or

the logging application. The faults are also reported

through the general fault warning indication.

8.4 Indication of faults related to voice alarm zones

(option with requirements)
The VACIE may have provision for an indication of faults

related to voice alarm zones. In this case the short-circuit

or interruption of a voice alarm transmission path

between the VACIE and the loudspeakers in that zone

shall be indicated by means of a separate light emitting

indicator per zone and/or an alphanumeric display.

Faults that occur in the Praesideo system are reported

per defective input or output for fault allocation. When an

individual fault is reported the name of the event

originator (i.e. the location of the fault) is provided.

The installer must give audio outputs that are assigned to a

zone, clear names, identifying the zone. This way the event

originator field in the indication of the individual fault will

immediately show in which zone the fault has occurred.

Praesideo provides zone fault status indicators, assigned

to keypad kits. One or more zones can be configured to

control such an indicator.

8.5 System fault

Praesideo is compliant.

A system fault is a fault as specified in 14.4 Program

monitoring (see also Annex C)or 14.6 Monitoring of

memory contents in the case of software controlled

VACIE. A system fault may prevent requirements of this

European Standard, other than those specified below,

from being fulfilled. In the event of a system fault at least

the following shall apply:

14.4 Program monitoring (see also Annex C)

a

a system fault shall be visibly indicated by means of

the general fault warning indicator and a separate

light emitting indicator on the VACIE. These

indications shall not be suppressed by any other

functional condition of the VACIE and shall remain

until a manual reset and/or another manual operation

at access level 2 or 3;

System faults are individually reported by the Praesideo

system and can be inspected using the front panel menu

of the network controller or the logging application.

Faults are also reported through a general fault warning

indicator, connected to a control output that is configured

as Fault alarm buzzer or visual Fault alarm indicator.

Both the individual fault indicator of each system fault

and the general fault warning indicator are not

suppressed by any other functional condition of the

Praesideo system.

b

a system fault shall be audibly indicated. This

indication may be capable of being silenced.

A control output contact of a Praesideo system component

can be configured as Fault alarm buzzer. This output

contact can be connected to a buzzer. This way all faults,

including system faults, are indicated audibly.

The Fault alarm buzzer can be silenced by

acknowledging all faults via a key or control input that is

configured as Fault acknowledge key. The control output

for the visual Fault alarm indicator is only deactivated

upon resolving and resetting all fault conditions.

8.6 Audible indication

Praesideo is compliant.

8.6.1 The audible indication of faults required in 8.2 shall

be capable of being silenced manually at access level 1

or 2 at the VACIE. The same manual operation may be

used as for silencing the voice alarm condition.

The Fault alarm buzzer can be silenced by

acknowledging all faults via a key or control input that is

configured as Fault acknowledge key. Individual faults

can also be acknowledged from the front panel menu of

the network controller or via the Open Interface.

Clause / Requirement

Compliance

Signature

Advertising