Инструкция по эксплуатации Bosch Praesideo 4.0

Страница 80

Advertising
background image

Praesideo 4.0

en | 90

Bosch Security Systems B.V.

IUI-PRAESIDEO_4.0 | V1.0 | 2013.01

Installation and User Instructions

7.2.2 Where a voice signal is used as part of the alert

signal, the alert signal shall precede the first pre-

recorded voice message for 3 s to 10 s. Successive alert

signals and messages shall then continue until either

automatically or manually changed or silenced. The

interval between successive messages shall not exceed

30 s and alert signals shall be broadcast whenever

periods of silence might otherwise exceed 10 s.

Praesideo offers this functionality via its call macros. The

installer must configure the call macros accordingly.

7.2.3 Where more than one alert signal is provided, each

signal shall be clearly distinguishable.

Praesideo offers a wide choice of independent alert and

alarm signals.

7.3 Evacuate signal
7.3.1 The evacuate signal may be preceded by an alert

signal (see 7.2).

The use of an alert signal, together with an evacuate

signal, should be assessed as part of an emergency

management plan (see ISO 7240-19). For buildings and

structures where the plan requires the unassisted

evacuation of occupants, the s.s.e.p. may be configured

to generate a warning signal that does not incorporate an

alert signal.

Praesideo offers the possibility to configure a call macro

with an evacuation signal or evacuation message only.

7.3.2 The evacuate signal shall include the tone signal

and pre-recorded voice messages, as specified in ISO

8201.

Manufacturers may implement other signal templates to

satisfy specific mandated national requirements.

The installer must configure one of the dedicated

ISO8201 compliant evacuate signals that Praesideo

offers. These emergency signals have the temporal

pattern as described by ISO8201 and have a predefined

name

‘Emg x ISO8201 C’, with x being a sequential number.

The installer must ensure that the sound pressure level

of the evacuate signal is at least 65dBA, or 75dBA if the

signal is intended to arouse sleeping occupants.

ISO8201 does not specify pre-recorded voice messages,

but Praesideo offers the possibility to store and select

custom voice messages to satisfy specific mandated

national requirements.

7.5 Audible warning - Optional function
7.5.3 The audible warning shall be silenced

automatically when the s.s.c.i.e. is reset from the voice

alarm condition.

Praesideo silences the audible warning signal upon

acknowledge of the voice alarm condition. Acknowledge

and reset can be combined in a single action.

7.6 Delay before entering the voice-alarm condition -

Optional function
d It shall be possible to override the delay by a manual

operation at access level 1 and/or by a signal from a

manual call point.

Since the Praesideo system does not process the fire

sensors, this functionality is better handled by the device

managing the fire sensors (the CIE). The Praesideo

system itself does not implement this requirement.

7.7 Phased evacuation - Optional function
c When switching from phased evacuation to manual

mode, the phased evacuation sequence shall halt.

Praesideo has multiple priority levels to override (phased

evacuation) calls by manually activated calls.

d When switching from manual mode to phased

evacuation, the phased evacuation sequence shall

resume from the point at which it was halted.

Praesideo will resume manually overruled calls without

live speech but with emergency priority, after the

overruling call has finished.

Clause / Requirement

Compliance

Signature

8 Fault-warning condition
8.1 Reception and processing of fault signals
8.1.2
The s.s.c.i.e. shall be capable of simultaneously

recognizing all of the faults specified in 8.2, and in 8.3 if

provided, unless this is prevented by

• the presence of voice-alarm signals in the same

emergency loudspeaker zone, and/or

• the

disablement

of

the corresponding emergency

loudspeaker zone or function, and/or

• the testing of a corresponding zone or function.

In Praesideo supervision is always active.

8.2 Indication of faults in specified functions
8.2.2
If the indication is by means of separate light-

emitting indicators, these may be the same as those

used to indicate disablement and/or testing of the

corresponding emergency loudspeaker zones or

functions.

Praesideo uses separate indicators for faults.

The optional disablement and test conditions are not

supported by the Praesideo system.