Installation and User Instructions

5

information on the communication parameters

employed on each transmission path,

6

recommended cable parameters for each

transmission path, and

7

fuse ratings;

c

specified means to limit the consequences of fault

(see 13.5.2);

The IUI describes the following means to limit the

consequences of fault:

Switchover to spare (standby) amplifiers

Audio/control input supervision

Backup power supply

Redundant network cabling

Loudspeaker line supervision

The ability of the emergency call station to make a

‘fail safe’ call in case of a network controller defect

A/B group wiring of loudspeakers

The ability of the multi channel interface to bypass

routing in case of a fatal fault in the MCI

d

configuring and commissioning instructions;

Configuring and commissioning instructions are included

in the IUI.

e

operating instructions;

Operating instructions are included in the IUI.

f

maintenance information.

Maintenance information of the Praesideo system are

included in the IUI.

13.2.2 The manufacturer shall prepare design

documentation that shall be submitted to the testing

authority together with the VACIE. This documentation

shall include drawings, parts lists, block diagrams, circuit

diagrams and a functional description to such an extent

that compliance with this European Standard may be

checked and that a general assessment of the

mechanical and electrical design is made possible.

All of the mentioned design documentation is available

as TPD for inspection by testing authorities.

13.3 Mechanical design requirements

Praesideo is compliant.

13.3.1 The cabinet of the VACIE shall be of robust

construction consistent with the method of installation

recommended in the documentation. It shall meet at

least classification IP30 of EN 60529:1991+A1:2000.

The Praesideo call station product range, network splitter

and fiber interfaces comply with this requirement. The

installer must implement this requirement for 19”-units,

by means of using a correct 19”- frame, meeting at least

classification IP30 of EN 60529:1991+A1:2000. The EN

54-16 certification of Praesideo includes the 19»-rack. A

rack must be used from the list of approved racks.

13.3.2 All interconnections and settings inside the

cabinet shall be accessible at level 3.

The installer must ensure that the physical access to the

Praesideo system is restricted to access level 3, then

accessibility to all interconnections and settings inside

the cabinet (e.g. interconnections between the system

elements) is restricted to this access level.

13.3.3 The VACIE may be housed in more than one

cabinet. If the documentation shows that the cabinets

may be installed in locations distributed within the

protected premises, then all of the mandatory manual

controls and indicators shall be on one cabinet or on

cabinets declared to be only suitable for mounting

adjacent to each other.

The IUI shows that the Praesideo cabinets may be

installed in locations distributed within the premises. One

dedicated Praesideo call station with call station

keypad(s) or call station kit with call station keypad kit(s)

can then be used for all of the mandatory controls and

indicators. The installer shall take care of proper

installation in order to fulfill this requirement.

13.3.4 All mandatory manual controls and light emitting

indicators shall be clearly labeled to indicate their

purpose. The labels shall be legible at 0.8 m distance in

an ambient light intensity from 100 lux to 500 lux.

The Praesideo call station keypad has a paper slot next

to each of its programmable keys. The installer must

provide proper labels that fit into these paper slots and

implement this requirement. Note that if the call station

keypad kit is used, the installer must provide custom-

made call station keypads, including the labels. A regular

font with with characters of 3 mm height offers sufficient

readability in case of high contrast between text color

and background. Lower contrast color selections will

require bigger characters.

13.3.5 The terminations for transmission paths and the

fuses shall be clearly labeled.

All terminations for transmission paths are clearly

labeled on all of the Praesideo system elements (near

the relevant connectors).

The mains fuse for each Praesideo system element that

has a mains connector is labeled on the rear plate of the

element.

Internal fuses have a parts code indication on the Printed

Circuit Board on which they are mounted. These fuses

may only be replaced by qualified service personnel

having access to the service documentation.

Clause / Requirement

Compliance

Signature