Инструкция по эксплуатации Bosch Praesideo 4.0

Страница 85

Advertising
background image

Praesideo 4.0

en | 95

Bosch Security Systems B.V.

IUI-PRAESIDEO_4.0 | V1.0 | 2013.01

Installation and User Instructions

Clause / Requirement

Compliance

Signature

14 Design requirements
14.1 General requirements and manufacturer's

declarations
14.1.2
In order to assist the process of design inspection,

the manufacturer shall declare in writing that
a the design has been carried out in accordance with a

quality management system that incorporates a set of

rules for the design of all elements of the s.s.c.i.e.

[e.g. ISO 9001].

The Bosch Security Systems development department

responsible for development / maintenance of the

Praesideo system works according its own development

process, Standard Development Process or SDP, which

is created using the CMMI model. The SDP implements

all process areas at maturity level 2 of the CMMI model,

and some process areas at maturity level 3 of the CMMI

model.

Rules for the design of all elements of the Praesideo

system can be found in the SDP repository. In the SDP

repository all process descriptions, process

implementation documents, templates, guidelines, etc. of

the development processes can be found.

The SDP repository is a version control system.

Bosch Security Systems is ISO9001 certified.

14.8.6 Mandatory indications on an alphanumeric display

shall be legible for the lesser of 1 h or the duration of the

standby power source, following the display of a new

indication of a functional condition, at 0,8 m distance in

ambient light intensities from 5 lx to 500 lx and at any

angle from the normal to the plane of the display up to

• 22,5° when viewed from each side;

• 15° when viewed from above and below.

Following the lesser of 1 h or the duration of the standby

power source, the indications shall be legible at 100 lx to

500 lx at the above distance and angles. It shall be

possible to re-establish the legibility at 5 lx to 100 lx by

means of a manual operation at access level 1.

If the Praesideo system enters the voice alarm condition

the display of the network controller will automatically

show the 'Emergency' menu. This indication stays on as

long as the system is in the voice alarm condition (i.e.

until the voice alarm condition is reset).

If the Praesideo system enters the fault warning

condition the display of the network controller will

automatically show the 'Faults' menu with the current

number of active faults. This indication stays on until

either the rotary knob of the network controller is used to

navigate through the menu, or the system enters the

voice alarm condition. The 'Faults' menu will always be

present in the Network Controller menu. Individual faults

are present in this 'Faults' menu until they are reset or

until they are overwritten by newer faults The menu can

show up to 200 individual faults after which the oldest

faults are deleted when new faults occur.

The display of the Network Controller complies with the

legibility demands of this clause.

14.10 Audible indication
14.10.2
The minimum sound level, measured under

anechoic conditions, at a distance of 1 m with any

access door on the s.s.c.i.e. closed, shall be either

• 60 dBA for voice-alarm indications and 50 dBA

for fault-warning indications, or

• 85 dBA for voice-alarm indications and 70 dBA

for fault-warning indications.

NOTE The allowance for two sets of audible indications

contemplates some s.s.c.i.e. being installed in normally

occupied areas (such as a security room). The selection

of an appropriate sound level can be controlled by

national requirements.

The installer must connect the buzzer that is provided

with Praesideo and complies with the sound levels

according to the first option, or use a different buzzer

with sound levels according to the second option. The

selection depends on the background noise on the

location where Praesideo is installed or by national

requirements.

14.12.3 Frequency response of s.s.c.i.e.

The frequency response requirements of ISO7240-16,

clause 14.12.3 are less stringent than required by EN54-

16, clause 13.12.3.

The Praesideo sound paths are within the specified limits

of this clause.

Advertising