Installation and User Instructions
13.8.3 Mandatory indications on an alphanumeric
display shall be legible for at least one hour following the
display of a new indication of the voice alarm condition
and at least
5 minutes for fault or disablement conditions, at 0,8 m
distance, in ambient light intensities from 5 to 500 lux, at
any angle from the normal to the plane of the display up
to
•
22.5º when viewed from each side, and
•
15º when viewed from above and below.
If the Praesideo system enters the voice alarm condition
the display of the network controller will automatically
show the ‘Emergency’ menu. This indication stays on as
long as the system is in the voice alarm condition (i.e.
until the voice alarm condition is reset).
If the Praesideo system enters the fault warning
condition the display of the network controller will
automatically show the ‘Faults’ menu with the current
number of active faults. This indication stays on until
either the rotary knob of the network controller is used to
navigate through the menu, or the system enters the
voice alarm condition. The ‘Faults’ menu will always be
present in the Network Controller menu. Individual faults
are present in this ‘Faults’ menu until they are reset or
until they are overwritten by newer faults The menu can
show up to 200 individual faults after which the oldest
faults are deleted when new faults occur.
The display of the Network Controller complies with the
legibility demands of this clause.
13.9 Indication colors
Praesideo is compliant.
13.9.1 The colors of the general and specific indications
from light emitting indicators shall be
a
red for indications of voice alarms;
The system status LED of Praesideo call stations is on
(red) when the system is in the voice alarm condition.
The installer must connect a red light emitting indicator to
an ‘Emergency alarm indicator’ output contact of the
Praesideo system. The key of a call station keypad kit
shall be configured to the action ‘Zone status’. The
installer must connect a red LED to the appropriate
control output belonging to this key.
b
yellow for indications of
1
fault warnings, and
2
disablements, or
The Power/Fault LED of Praesideo call stations is yellow
(on or flashing) when the system is in the fault warning
condition. The installer must connect a yellow light
emitting indicator to the ‘Fault alarm indicator’ output
contact (or another output contact configured for this
function). A call station key indicator lights up yellow
when the key is configured to the action ‘Reset fault’ or
‘Ack and reset’ and the system enters the fault warning
condition.
Disablement indication is not available in the Praesideo
system since Praesideo does not support the optional
disablement condition.
c
green for the indication that the VACIE is supplied
with power.
All light emitting indicators of the Praesideo system that
indicate power supply are green.
NOTE - Where voice alarm automatic message status
indicators are provided, it may be advantageous to
indicate the difference between evacuation and alert
messages. In this case, red will be used for emergency
messages and yellow may be used for alert messages.
13.9.2 The use of different colors is not necessary for
indications on alphanumeric displays. However, if
different colors are used for different indications, the
colors used shall be as specified in 13.9.1.
The alphanumeric displays used in the Praesideo
system do not use different colors for indications.
13.10 Audible indications
Praesideo is compliant.
13.10.1 Audible indicators shall be part of the VACIE.
The same device may be used for voice alarm zone
activated and fault warning indications.
The installer must connect buzzers to output contacts
configured as ‘Emergency alarm buzzer’ or ‘Fault alarm
buzzer’. The installer may decide to connect both the
voice alarm activated output contact as well as the fault
warning condition activated output contact in parallel to
the same buzzer.
13.10.2 The minimum sound pressure level, measured
under anechoic conditions at a distance of 1 m, with any
access door(s) on the VACIE closed, shall be
•
60 dBA for the voice alarm condition, and
•
50 dBA for the fault warning condition.
The installer must connect the buzzer, provided with
Praesideo, that complies with this clause.
Clause / Requirement
Compliance