13.8.3 Mandatory indications on an alphanumeric

display shall be legible for at least one hour following the

display of a new indication of the voice alarm condition

and at least

5 minutes for fault or disablement conditions, at 0,8 m

distance, in ambient light intensities from 5 to 500 lux, at

any angle from the normal to the plane of the display up

to

22.5º when viewed from each side, and

15º when viewed from above and below.

If the Praesideo system enters the voice alarm condition

the display of the network controller will automatically

show the ‘Emergency’ menu. This indication stays on as

long as the system is in the voice alarm condition (i.e.

until the voice alarm condition is reset).

If the Praesideo system enters the fault warning

condition the display of the network controller will

automatically show the ‘Faults’ menu with the current

number of active faults. This indication stays on until

either the rotary knob of the network controller is used to

navigate through the menu, or the system enters the

voice alarm condition. The ‘Faults’ menu will always be

present in the Network Controller menu. Individual faults

are present in this ‘Faults’ menu until they are reset or

until they are overwritten by newer faults The menu can

show up to 200 individual faults after which the oldest

faults are deleted when new faults occur.

The display of the Network Controller complies with the

legibility demands of this clause.

13.9 Indication colors

Praesideo is compliant.

13.9.1 The colors of the general and specific indications

from light emitting indicators shall be
a

red for indications of voice alarms;

The system status LED of Praesideo call stations is on

(red) when the system is in the voice alarm condition.

The installer must connect a red light emitting indicator to

an ‘Emergency alarm indicator’ output contact of the

Praesideo system. The key of a call station keypad kit

shall be configured to the action ‘Zone status’. The

installer must connect a red LED to the appropriate

control output belonging to this key.

b

yellow for indications of

1

fault warnings, and

2

disablements, or

The Power/Fault LED of Praesideo call stations is yellow

(on or flashing) when the system is in the fault warning

condition. The installer must connect a yellow light

emitting indicator to the ‘Fault alarm indicator’ output

contact (or another output contact configured for this

function). A call station key indicator lights up yellow

when the key is configured to the action ‘Reset fault’ or

‘Ack and reset’ and the system enters the fault warning

condition.

Disablement indication is not available in the Praesideo

system since Praesideo does not support the optional

disablement condition.

c

green for the indication that the VACIE is supplied

with power.

All light emitting indicators of the Praesideo system that

indicate power supply are green.

NOTE - Where voice alarm automatic message status

indicators are provided, it may be advantageous to

indicate the difference between evacuation and alert

messages. In this case, red will be used for emergency

messages and yellow may be used for alert messages.
13.9.2 The use of different colors is not necessary for

indications on alphanumeric displays. However, if

different colors are used for different indications, the

colors used shall be as specified in 13.9.1.

The alphanumeric displays used in the Praesideo

system do not use different colors for indications.

13.10 Audible indications

Praesideo is compliant.

13.10.1 Audible indicators shall be part of the VACIE.

The same device may be used for voice alarm zone

activated and fault warning indications.

The installer must connect buzzers to output contacts

configured as ‘Emergency alarm buzzer’ or ‘Fault alarm

buzzer’. The installer may decide to connect both the

voice alarm activated output contact as well as the fault

warning condition activated output contact in parallel to

the same buzzer.

13.10.2 The minimum sound pressure level, measured

under anechoic conditions at a distance of 1 m, with any

access door(s) on the VACIE closed, shall be

60 dBA for the voice alarm condition, and

50 dBA for the fault warning condition.

The installer must connect the buzzer, provided with

Praesideo, that complies with this clause.