Clause / Requirement
Compliance
Signature
13 Design requirements
13.1 General requirements and manufacturer's
declarations
Praesideo is compliant.
13.1.1 The VACIE shall comply with the design
requirements of this clause, where relevant to the
technology used. Some requirements can be verified by
testing. Others can only be verified by inspection of the
design and its accompanying documentation because of
the impracticability of testing all of the possible
combinations of functions and of establishing the long-
term reliability of the VACIE.
See the relevant clauses regarding testing and
documentation.
13.1.2 In order to assist the process of design
inspection, the manufacturer shall declare the following
in writing:
a
that the design has been carried out in accordance
with a quality management system which
incorporates a set of rules for the design of all
elements of the VACIE;
The Bosch Security Systems development department
responsible for development/maintenance of the
Praesideo system works according its own development
process, Standard Development Process or SDP, that is
created using the CMMI model. The SDP implements all
process areas at maturity level 2 of the CMMI model, and
some process areas at maturity level 3 of the CMMI
model.
Rules for the design of all elements of the Praesideo
system can be found in the SDP repository. In the SDP
repository all process descriptions, process
implementation documents, templates, guidelines, etc. of
the development processes can be found.
The SDP repository is a version control system.
b
that the components of the VACIE have been
selected for the intended purpose and are expected
to operate within their specification when the
environmental conditions outside the cabinet of the
VACIE comply with Class 3k5 of EN 60721-3-3:1995
+ A2:1997.
The components of the Praesideo system operate within
their specification within the specified environmental
conditions (Class 3k5 of EN 60721-3-3:1995 + A2:1997).
This is verified by means of testing and is documented in
the test reports. The 19»-racks for Praesideo are part of
the system and subject to certification. A rack must be
selected from the list of approved racks for this purpose.
13.2 Documentation
Praesideo is compliant.
13.2.1 The manufacturer shall prepare installation and
user documentation which shall be submitted to the
testing authority together with the VACIE. This shall
comprise at least the following:
The Praesideo Installation and User Instructions (IUI) are
provided as multilingual pdf-files on the DVD that
contains the software for installation and configuration.
The IUI can also be downloaded from Extranet.
a
a general description of the equipment, including a
list of
The IUI contains a general description of the Praesideo
system. It includes an EN54-16 checklist, containing a
list of supported optional functions.
It describes all Praesideo functions related to EN54-16 or
otherwise.
1
the optional functions with requirements of this
European Standard,
See this checklist, clause 4.1.1.
2
the functions relating to other parts of EN 54, and
3
the ancillary functions not required by this
European Standard;
b
technical specifications of the inputs and outputs of
the VACIE, sufficient to permit an assessment of the
mechanical, electrical, and software compatibility
with other components of the system (e.g. as
described in EN 54-1), including where relevant
The inputs and outputs for audio and control are described
in the IUI, including the technical data, system functions,
configuration instructions, compliancy to standards. This
includes the information as requested in 13.2.1 b) 1)..7).
The Open Interface is described in the ‘Open Interface
Programming Instructions’ (OIPI). This document is
always delivered together with the Praesideo system as
a pdf-file on the distribution DVD. This document gives
enough information for third party programmers to create
applications to control or display Praesideo functions.
1
the power requirements for recommended
operation,
2
the maximum number of voice alarm zones,
3
information concerning the connection of
emergency microphones,
4
the maximum and minimum electrical ratings for
each input and output,