Excluded clauses – Инструкция по эксплуатации Bosch Praesideo

Страница 78

Advertising
background image

Bosch Security Systems | 2011-02

Praesideo 3.5

| Installation and User Instructions | ISO7240-16: 2007

en

| 80

Excluded clauses

Clause / Requirement

Compliance

Signature

EN54-16, clause 12.1 Emergency microphone - option with
requirements.
c Where a pre-announcement attention drawing signal is

provided, an indicator adjacent to the microphone shall

show when the signal has finished and live speech can

commence.

This clause is not part of ISO7240-16.

Clause / Requirement

Compliance

Signature

EN54-16, clause 13.4.1 Electrical and other design
requirements

The processing of signals shall give the highest priority to the

voice alarm condition.

This clause is not part of ISO7240-16.

EN54-16, clause 13.13 Message store(s)

Pre-recorded messages shall be stored in non-volatile memory

that retains the messages when all power sources are

removed.

NOTE The use of tapes or magnetic or optical data disks for
the storage of emergency messages is not acceptable at the
time of drafting this European Standard
(see Annex C)

The NOTE is not part of ISO7240-16.

Advertising