Excluded clauses – Инструкция по эксплуатации Bosch Praesideo
Страница 78
Bosch Security Systems | 2011-02
Praesideo 3.5
| Installation and User Instructions | ISO7240-16: 2007
en
| 80
Excluded clauses
Clause / Requirement
Compliance
Signature
EN54-16, clause 12.1 Emergency microphone - option with
requirements.
c Where a pre-announcement attention drawing signal is
provided, an indicator adjacent to the microphone shall
show when the signal has finished and live speech can
commence.
This clause is not part of ISO7240-16.
Clause / Requirement
Compliance
Signature
EN54-16, clause 13.4.1 Electrical and other design
requirements
The processing of signals shall give the highest priority to the
voice alarm condition.
This clause is not part of ISO7240-16.
EN54-16, clause 13.13 Message store(s)
Pre-recorded messages shall be stored in non-volatile memory
that retains the messages when all power sources are
removed.
NOTE The use of tapes or magnetic or optical data disks for
the storage of emergency messages is not acceptable at the
time of drafting this European Standard
(see Annex C)