Bosch Security Systems | 2011-02

Praesideo 3.5

| Installation and User Instructions | ISO7240-16: 2007

en

| 76

Clause / Requirement

Compliance

Signature

14 Design requirements

14.2 Documentation

14.2.1

The manufacturer shall prepare installation and user

documentation, which shall be submitted to the testing

authority together with the s.s.c.i.e. This shall comprise at least

the following:
b technical specifications of the inputs and outputs of the

s.s.c.i.e., sufficient to permit an assessment of the

mechanical, electrical, and software compatibility with other

components of the system (e.g. as described in

ISO 7240-1), including where relevant

3 the maximum number of alarm inputs from an emergency

detection system

The inputs and outputs for audio and control are described in

the IUI, including the technical data, system functions,

configuration instructions, compliancy to standards. This

includes the information as requested in 14.2.1 b 3.

c installation information, including

The IUI contains all information as requested in 14.2.1 c

1-5.

1 the suitability for use in various environments,
2 how the requirements of 14.3.3 and 14.5.3 can be met if

the s.s.c.i.e. is contained in more than one cabinet,

3 how the requirements of 14.3.3 and 14.5.4 can be met if

the s.s.c.i.e is designed to be used with power-supply

equipment contained in a separate cabinet,

4 mounting instructions, and
5 instructions for connecting the inputs and outputs.

14.3.3

The s.s.c.i.e. may be housed in more than one cabinet. If

the documentation shows that the cabinets may be installed in

locations distributed within a site, then all of the mandatory

manual controls and indicators shall be on one cabinet or on

cabinets declared to be suitable only for mounting adjacent to

each other.

NOTE

For the purposes of 14.3.3, adjacent cabinets are those

that are mounted in physical contact with each other.

In case Praesideo is installed in multiple cabinets in locations

distributed within a site, the installer must arrange that all

mandatory manual controls and indicators are on the same

location, either by installing them on a single cabinet or on

adjacent cabinets that are mounted in physical contact with

each other.

14.8 Indications on alphanumeric displays

14.8.2

Alphanumeric displays used for mandatory indications

shall have at least one clearly distinguishable window,

consisting of at least two clearly identifiable fields.

The display of the network controller is used to display

mandatory indications. It consists of two separate lines of text,

each representing a specific field, clearly identifiable.

14.8.3

If not included in the displayed information, the purpose

of each field shall be clearly labelled.

Indication of the voice alarm condition is by means of the text

'Emergency' and the name of the key that activated the voice

alarm condition. Indication of the fault warning condition is by

means of the text 'Faults' and an indication of the number of

active faults in the system. Individual faults with details are

shown in a menu structure.

14.8.4

Where roman characters are used, a field shall be

capable of containing at least the following:
a at least 16 characters where the display of a functional

condition uses a cross-reference to other information to

identify the location;

The display of the network controller consists of two lines with

16 characters each. It uses a menu with rotary knob navigation

to select additional detailed information about functional

conditions.

b at least 40 characters where the display is intended to

include the complete information on the location of a

functional condition.

Not applicable, see 14.8.4.a.

14.8.5

Where other characters are used, a field shall be

capable of containing at least the following:

Not applicable, see 14.8.4.

a at least 4 characters where the display of a functional

condition uses a cross-reference to other information to

identify the location;

b at least 8 characters where the display is intended to include

the complete information on the location of a functional

condition.

14.9 Colours of indications

14.9.1

The colours of the general and specific indications from

light-emitting indicators shall be as follows:
b yellow for indications of

3 emergency loudspeaker zones in the test state.

The test condition is an optional function and is not supported

by Praesideo. See 10.