Инструкция по эксплуатации Bosch Praesideo

Страница 73

Advertising
background image

Bosch Security Systems | 2011-02

Praesideo 3.5

| Installation and User Instructions | ISO7240-16: 2007

en

| 75

9.3.3

The same light-emitting indicator may be used as that for

the indication of the corresponding fault, although the

indication shall be distinguishable. The same light-emitting

indicator and the same indication may be used to indicate a

disabled emergency loudspeaker zone and an emergency

loudspeaker zone under test.

The optional disablement condition is not supported by the

Praesideo system.

Clause / Requirement

Compliance

Signature

10 Test condition - Optional function

The optional test condition is not supported by the Praesideo

system.

Clause / Requirement

Compliance

Signature

11 Manual mode control - Optional function

11.1.2

In the manual mode, the receiving and display of signals

shall not be inhibited.

Praesideo does not inhibit the receiving and display of signals

in the manual mode.

11.1.3

In the manual mode, any phased evacuation sequence

shall be halted. Returning the system to automatic mode shall

reinstate the phased evacuation sequence as if it had not been

halted.

Praesideo will resume manually overruled calls after the

overruling call has finished, providing that the overruled call was

without live speech and had emergency priority.

Clause / Requirement

Compliance

Signature

13 Emergency microphone - Optional function

13.1 General
c The emergency microphone control shall mute alert and

evacuate signals within the selected emergency

loudspeaker zone.

If the configured call of the emergency microphone was given a

higher priority than the calls that generate alert and evacuate

signals within the same emergency loudspeaker zone, these

calls will be aborted and mute.

d Use of the emergency microphone shall not reset an existing

functional condition. After the microphone is no longer

used, the functional condition shall be re-established.

Praesideo will resume overruled calls after the overruling call

has finished, providing that the overruled call was without live

speech and had emergency priority.

The emergency state that was entered upon starting a call with

emergency priority, will remain until explicitly manually reset.

e Unless 13.3 applies, the microphone shall broadcast voice

messages to a pre-configured set of emergency

loudspeaker zones.

Praesideo allows for free assignment of emergency

loudspeaker zones to calls that may contain live speech or

prerecorded messages.

This assignment can be manually during operation or in

advance during configuration.

13.2 Microphone priority - Optional function

13.2.2

Where more than one microphone is configured at each

priority level, only one microphone shall be active at any one

time. If more than one microphone at the same priority is

activated, the most recently activated microphone shall be

enabled.

Praesideo allows more than one microphone to be configured

for calls with the same priority, but in that case typically the

most recently activated one will not be enabled until the

previous one has finished, i.e. first come, first served. Only in

case of the highest priority, 255, multiple calls with this priority

act on overruling basis, i.e. the most recently activated

microphone will be enabled.

Only one microphone will be active at any one time in the same

zone.

13.3 Microphone emergency loudspeaker zone
control - Optional function
The s.s.c.i.e. may be configurable to route microphone

messages to groups of emergency loudspeaker zones, with

each group containing at least one emergency loudspeaker

zone.

Praesideo allows for configuration of zone groups, containing

one or more emergency loudspeaker zones. Calls can be made

to a free selection of zones and zone groups.

Advertising