Praesideo 3.5 | Инструкции по установке и эксплуатации | EN54-16: 2008

ru | 46

Пункт / требование

Соответствие

Подпись

9 Disablement condition (option with requirements)

В системе Praesideo не реализована индикация

нерабочего состояния.

9.1 General requirements
9.1.1
Disablements in accordance with the requirements

of 9.4 shall inhibit all corresponding mandatory

indications and/or outputs but shall not prevent other

mandatory indications and/or outputs.
9.1.2 The VACIE shall have provision to independently

disable and re-enable the function specified in 9.4 by

means of manual operations at access level 2.
9.1.3 The VACIE shall be in the disabled condition while

a disablement in accordance with the requirements of 9.4

exists.
9.1.4 Disablement and re-enablement shall not be

affected by a reset from the voice alarm condition or from

the fault warning condition.
9.2 Indication of the disabled condition
The disabled condition shall be indicated visibly, by

means of
a

a separate light emitting indicator (the general

disablement indicator), and

b

an indication for each disablement, as specified in

9.3 and 9.4.

9.3 Indication of specific disablements
9.3.1
Disablements shall either be indicated within 2 s of

the completion of the manual operation or, where a

disablement cannot be completed within 2 s, it shall be

indicated within 2 s that the disabling process is running.
9.3.2 The same light-emitting indicator may be used as

that for the indication of the corresponding fault, although

the indication shall be distinguishable.
9.3.3 If the indication is on an alphanumeric display,

which cannot simultaneously indicate all of the

disablements because of its limited capacity, at least the

following shall apply:
a

the presence of disablement indications which have

been suppressed shall be indicated;

b

suppressed disablement indications shall be capable

of being displayed by means of a manual operation

at access level 1 or 2 which interrogates only

disablement indications.

9.4 Disablements and their indication
Voice alarm zones may be capable of being

independently disabled and re-enabled. In this case the

disablements shall be indicated by means of separate

light emitting indicators per zone and/or an alphanumeric

display. The indications shall not be suppressed during

the voice alarm condition.
9.5 Transmission of the disablement condition
The VACIE shall have provision for transmitting, by

means of a general disablement signal, all disablement

conditions specified in this clause.