Changed clauses – Инструкция по эксплуатации Bosch Praesideo
Страница 75
Bosch Security Systems | 2011-02
Praesideo 3.5
| Installation and User Instructions | ISO7240-16: 2007
en
| 77
Changed clauses
Clause / Requirement
Compliance
Signature
17 Tests
All tests as asked for in the clauses of section 17 have been
carried out by an accredited certification body for ISO7240-16
compliancy.
The Praesideo system has been found compliant to ISO7240-
16 and received a certification of compliancy.
Clause / Requirement
Compliance
Signature
18 Test report
The tester must take care of documenting the testing
programme and the results of the tests in a test report that at
least contains the information as listed in clause 18.
Clause / Requirement
Compliance
Signature
4.3 Power supply
Power-supply equipment shall comply with the requirements of
ISO 7240-4 and may be internal or external to the s.s.c.i.e.
cabinet.
The power supply may be shared with that of the emergency
detection system.
The installer must use power supplies and battery charging
equipment in accordance with ISO7240-4, with separate
wiring for mains (230Vac) and battery backup (48Vdc) from the
power supply to the Praesideo system.
The power supply equipment must be installed in a separate
cabinet, not shared with the Praesideo system, unless the
combination of the actual power supply equipment and
Praesideo system elements in the same cabinet has been
certified.
The content of the ISO7240-16 certification is subject to
change. The most recent version of this certificate can be found
on www.boschsecurity.com.
The network controller and all amplifiers are supplied with a
mains supply and DC backup supply (48V) input. Switch over
between the both takes place automatically, without any
interruption or status change other than the power supply
related indications.
The installer must ensure that the output voltages of the power
supply equipment do not exceed the specifications of the mains
and battery inputs of the connected Praesideo equipment.
Clause / Requirement
Compliance
Signature
8 Fault-warning condition
8.5 Reset of fault indications
8.5.2
Following the completion of the reset process, the
indication of the correct functional conditions corresponding to
any received signals shall either remain or be re-established
within 100 s
.
If any individual fault is reset while it is not actually resolved in
the system, the Praesideo system will report the fault again
within 100 seconds. If all faults are reset in one action, all
individual faults that are not actually resolved in the system are
reported again within 100 seconds.
Clause / Requirement
Compliance
Signature
9 Disabled condition - Optional function
9.3 Indication of specific disablements
9.3.4
If the indication is on an alphanumeric display that cannot
simultaneously indicate all of the disablements because of its
limited capacity, at least the following shall apply.
Praesideo does not support the optional function disabled
condition. See 9.
b Suppressed disablement indications shall be capable of
being displayed, independently of other indications, by
means of a manual operation at access level 1 or 2, which
interrogates only the disablement indications.