Changed clauses – Инструкция по эксплуатации Bosch Praesideo

Страница 75

Advertising
background image

Bosch Security Systems | 2011-02

Praesideo 3.5

| Installation and User Instructions | ISO7240-16: 2007

en

| 77

Changed clauses

Clause / Requirement

Compliance

Signature

17 Tests

All tests as asked for in the clauses of section 17 have been

carried out by an accredited certification body for ISO7240-16

compliancy.

The Praesideo system has been found compliant to ISO7240-

16 and received a certification of compliancy.

Clause / Requirement

Compliance

Signature

18 Test report

The tester must take care of documenting the testing

programme and the results of the tests in a test report that at

least contains the information as listed in clause 18.

Clause / Requirement

Compliance

Signature

4.3 Power supply

Power-supply equipment shall comply with the requirements of

ISO 7240-4 and may be internal or external to the s.s.c.i.e.

cabinet.

The power supply may be shared with that of the emergency

detection system.

The installer must use power supplies and battery charging

equipment in accordance with ISO7240-4, with separate

wiring for mains (230Vac) and battery backup (48Vdc) from the

power supply to the Praesideo system.

The power supply equipment must be installed in a separate

cabinet, not shared with the Praesideo system, unless the

combination of the actual power supply equipment and

Praesideo system elements in the same cabinet has been

certified.

The content of the ISO7240-16 certification is subject to

change. The most recent version of this certificate can be found

on www.boschsecurity.com.

The network controller and all amplifiers are supplied with a

mains supply and DC backup supply (48V) input. Switch over

between the both takes place automatically, without any

interruption or status change other than the power supply

related indications.

The installer must ensure that the output voltages of the power

supply equipment do not exceed the specifications of the mains

and battery inputs of the connected Praesideo equipment.

Clause / Requirement

Compliance

Signature

8 Fault-warning condition

8.5 Reset of fault indications

8.5.2

Following the completion of the reset process, the

indication of the correct functional conditions corresponding to

any received signals shall either remain or be re-established

within 100 s

.

If any individual fault is reset while it is not actually resolved in

the system, the Praesideo system will report the fault again

within 100 seconds. If all faults are reset in one action, all

individual faults that are not actually resolved in the system are

reported again within 100 seconds.

Clause / Requirement

Compliance

Signature

9 Disabled condition - Optional function

9.3 Indication of specific disablements

9.3.4

If the indication is on an alphanumeric display that cannot

simultaneously indicate all of the disablements because of its

limited capacity, at least the following shall apply.

Praesideo does not support the optional function disabled

condition. See 9.

b Suppressed disablement indications shall be capable of

being displayed, independently of other indications, by

means of a manual operation at access level 1 or 2, which

interrogates only the disablement indications.