11 Приложение

VEGAFLEX 86 • Протокол Modbus и Levelmaster

42288-R

U-130320

Assign Unit Number

Request:

Параметр

Length

Code/Data

Assign Unit Number

6 characters ASCII

UuuNnn

Response:

Параметр

Length

Code/Data

Assign Unit Number

6 characters ASCII

UuuNOK
uu = new Address

Set number of Floats

Request:

Параметр

Length

Code/Data

Set number of Floats

5 characters ASCII

UuuFn

Response:

Параметр

Length

Code/Data

Set number of Floats

6 characters ASCII

UuuFOK

Если число установлено на 0, уровень возвращаться больше не будет.

Set Baud Rate

Request:

Параметр

Length

Code/Data

Set Baud Rate

8 (12) characters ASCII

UuuBbbbb[b][pds]
Bbbbb[b] = 1200, 9600 (default)
pds = parity, data length, stop bit

(optional)
parity: none = 81, even = 71

(default), odd = 71

Response:

Параметр

Length

Code/Data

Set Baud Rate

11 characters ASCII

Пример: U01B9600E71
Устройство по адресу 1 изменить на скорость передачи 9600, четность - четный, 7 битов

данных, 1 стоповый бит