31

GB

10. Specifications

10-1. Product functions

• This controller can control up to 50 air conditioners and LOSSNAY with a daily schedule either

collectively or in groups.

• This controller has only a schedule setting function and must be used with another system

controller. When used independently, only the air conditioner's ON/OFF status and error status

will be monitored (operation status display). In addition to schedule setting, the units can be

turned ON/OFF and stopped and the timer can be reset either collectively or in groups with switch

operations.

The details of the functions are listed below.
<List of system remote controller functions>

Function Details

ON/OFF

ON/OFF operations can be carried out collectively or for each group.

Operation

Timer reset (*4)

The timer setting details can be disabled collectively.

Setting details

ON/OFF
COOL/HEAT
Room temperature adjustment (TEMP.)
Operation prohibit (ON/OFF, operation mode, setting temperature)

Number of settings

Number of setting patterns: 9
(Operation for a week can be set by selecting one of nine patterns for each
day.)
Number of operations: Up to 16 operations can be set in one pattern.

Timer

Time setting unit

The item can be set in five-minute units.

Time

The current time and day can be displayed.

Error

The address of the faulty unit and the error code are displayed on the LCD.

Normal

functions

Monitor

ON/OFF status (*5)

The ON/OFF status of the unit is displayed on the LCD when GROUP is
selected.

Group setting

Set the unit (indoor unit, LOSSNAY, remote controller, slave system
controller) group.

Operation

Interlocked unit setting

Set the LOSSNAY and indoor unit interlock.

Master system

controller/Slave system

controller (*1)

Set the master and slave system controllers.

Operation prohibit setting

Enable/disable

Set whether to prohibit operation with the local remote control using this
controller or with another controller.

Celsius/Fahrenheit display Set the set temperature display to a Celsius or Fahrenheit display.

Prohibit range

To prohibit an operation, set whether to prohibit only the remote controller or
to also prohibit the other controllers.

System remote control own

address

Set the schedule timer's address (Refer to the Installation Manual.)

External input

Emergency stop level input, ON/OFF level input, ON/OFF and operation
prohibit/enable pulse input

Default

setting

function

System

(*3)

External output

ON/OFF status output, error/normal state output

Indoor unit, LOSSNAY

Maximum 50 units

Number of indoor units and

LOSSNAY in one group

1 to 16 units (The indoor unit and LOSSNAY cannot be registered in the same
group.)

Number of local remote

controls in one group

0 to 2 units

Number of system

controllers that can be

controlled by one group (*2)

0 to 4 units (Note that this includes the number of local remote controllers
used in one group)
0 to 3 units in a group having one local remote controller

System

limits

Number of

registered

units

Number of indoor units

interlocked with one

LOSSNAY

0 to 16 units

(*1) Refer to page 30.
(*2) This controller (schedule timer) is one of the system controllers.
(*3) Refer to page 28.
(*4) Check the operation status (operation mode, set temperature, etc.) of other air conditioners with the system

controller being used.

(*5) These displayed details are the schedule setting details. These are not the air conditioner operation status

monitor details.