3-2. Schedule operation

This controller carries out schedule operation at each set time.
[Operation example] The schedule operation for pattern 1 given as an example in step 2. Setting of

program on the previous page is explained in this section.

8:15 - Start cooling operation at 29°C. Prohibit adjustment of the room temperature using the

local remote controller.

10:00 - Stop the air conditioner. Cancel the local remote controller room temperature

adjustment operation prohibit setting, and then prohibit ON/OFF operations.

10:15 - Resume operation at 27°C. Prohibit operation of the local remote controller.
12:00 - Stop the air conditioner. Prohibit ON/OFF operations using the local remote controller.
13:00 - Start cooling operation at 25°C. Prohibit adjustment of the room temperature using the

local remote controller.

17:00 - Stop the air conditioner. Cancel the local remote controller room temperature

adjustment operation prohibit setting.

21:00 - Stop the air conditioner. Prohibit ON/OFF operations using the local remote controller.

(The details set for the final operation will be held until schedule operation starts on the

next day.)

Prohibit

All enable

ON

OFF

Local remote
controller prohibit
state

Air conditioner
operation state

Room
temperature
adjustment

ON/OFF

Room
temperature
adjustment

ON/OFF

ON/OFF

8:15 10:00 10:15

12:00

13:00

15:00 15:15

17:00

21:00

24:00

29°C, cool

27°C, cool

25°C, cool

NOTE

1. Even if a schedule operation is being executed from this controller, the air conditioner can be operated using

the local remote controller.

2. Operations when "operation prohibit" is set

If "operation prohibit" is set from another system controller, the schedule operation of the set prohibit item
will not be executed.
The prohibit items set from the other system controllers are ON/OFF (

ON/OFF

), operation mode changeover

(

MODE

) and room temperature adjustment (

TEMP.

).

3. Operation when "operation mode changeover limit (season changing)" is set

If "operation mode changeover limit (season changing)" is set from another system controller,
"cooling/heating" operations following the schedule will not be executed.
When "cooling limit" is set, cooling operation following the schedule will not be executed.
When "heating limit" is set, heating operation following the schedule will not be executed.

4. Operation during power failure for this controller

The operations set in the schedule will not be executed during a power failure. When the power is recovered,
operation will resume with the schedule active after the restoration time. Note that if the schedule operation
contains "operation prohibit", the current state set in the schedule will be restored.