3. Outline of schedule setting and operation

3-1. Outline of setting

The schedule is set with this controller using the following procedures.
1. Setting of current time and day
2. Setting of program

Set the schedule pattern. (Up to nine types of operations patterns with 16 operations in each
pattern can be set.)

[Setting example]

Set details

Pattern Operation Set time

ON/OFF Mode Set

temp.

Operation

prohibit

1

8:15

ON

Cool 29°C

Room temp.

adjustment

2 10:00

OFF - - ON/OFF

Set the time to start schedule
operation, and the details of the
operation.

3 10:15

ON -

27°C

Enable

4 12:00

OFF - - ON/OFF

5 13:00

ON -

25°C

Room temp.

adjustment

6 17:00

OFF - - Enable

: : :

:

: :

1

16 21:00

OFF - - ON/OFF

With operation 1, cooling with the air
conditioner is started at 08:15,
operation is continued at 29°C, and
adjustment of the room temperature
with the local remote controller is
prohibited.

1

9:00

ON -

27°C

Room temp.

adjustment

: : :

:

: :

2

16 22:00

OFF - - ON/OFF

: : : :

:

:: :

1

8:30

ON

Heat 22°C

Room temp.

adjustment

: : :

:

: :

9

16 21:30

OFF - - ON/OFF

3. Setting of weekly program

Set the schedule pattern set in step 2 in day-units for each group.

[Setting example]

Day

Group

Sun. Mon. Tue. Wed. Thu. Fri. Sat.

1

Pattern 1 Pattern 2 Pattern 2 Pattern 2 Pattern 2 Pattern 2 Pattern 1

2

No setting Pattern 3 Pattern 3 Pattern 4 Pattern 4 Pattern 5 Pattern 6

:

50

Pattern 9 Pattern 7 Pattern 7 Pattern 8 Pattern 8 No setting Pattern 9

Pattern 1 is used for the

schedule operation on

Sunday in group 1.

Schedule operation is not

carried out on Sunday in

group 2.