Инструкция по эксплуатации VEGA VEGASON 65 Foundation Fieldbus

Страница 61

Advertising
background image

l

CAL_LEVEL_LO

-

M

in./max.-adjustment: Level at 'Cal_point_lo'. When writing 'Cal_level_lo' and 'Cal_type' = 1

(O

nline), the 'Cal_point_lo' is automatically set to the current sensor value. The unit is defined in

'L

evel_unit'

l

CAL_TYPE

-

M

in./max.-adjustment: Defines type of calibration: Dry: no influence of sensor value. Online:

current sensor value determines 'Cal_point_hi/lo'

l

level

-

V

alue after min./max.-adjustment

l

level_unit

-

U

nit code of 'Level', 'Level_offset', 'Cal_level_hi', 'Cal_level_lo'

l

level_offset

-

Off

set that is added to the 'Level' value. Unit derives from 'Level_unit'

l

SENSOR_OFFSET

-

Off

set that is added to the 'Sensor_value'. Unit derives from 'Sensor_range.unit'

l

end_of_operation_range

-

S

et up to suit the process conditions

l

begin_of_operation_range

-

S

et up to suit the process conditions

l

product_type

-

S

et up to suit the process conditions. If Special-Parameter adjustment has been utilized this

parameter cannot be written

l

liquids_medium_type

-

S

et up to suit the process conditions. If Special-Parameter adjustment has been utilized this

parameter cannot be written

l

solids_medium_type

-

S

et up to suit the process conditions. If Special-Parameter adjustment has been utilized this

parameter cannot be written

l

liquids_vessel_type

-

S

et up to suit the process conditions. If Special-Parameter adjustment has been utilized this

parameter cannot be written

l

solids_vessel_type

-

S

et up to suit the process conditions. If Special-Parameter adjustment has been utilized this

parameter cannot be written

l

fast_level_change

-

S

et up to suit the process conditions. If Special-Parameter adjustment has been utilized this

parameter cannot be written

l

rst_echo_factor

-

S

et up to suit the process conditions

l

pulse_velocity_correction

-

S

et up to suit the process conditions

l

echo_quality

-

S

ignal/Noise ratio

VEGASON

65 • F

oundation Fieldbus

61