– Possible types of linearization are: linear, user defined, cylindrical lying container, spherical

container

– "0: ""Linear"" 1: ""User def"" 20: ""Cylindrical lying container"" 21: ""Spherical container"""

curve_points_1_10

– X and Y values for the user defined linearization curve

curve_points_11_20

– X and Y values for the user defined linearization curve

curve_points_21_30

– X and Y values for the user defined linearization curve

curve_points_31_33

– X and Y values for the user defined linearization curve

curve status

– Result of table plausibility check

– "0: ""Uninitialized"" 1: ""Good"" 2: ""Not monotonous increasing"" 3: ""Not monotonous

decreasing"" 4: ""Not enough values transmitted"" 5: ""Too many values transmitted"" 6:

""Gradient of edge too high"" 7: ""Values not excepted"" 8: ""Table currently loaded"" 9:

""Sorting and checking table"""

SUB_DEVICE_NUMBER

SENSOR_ELEMENT_TYPE

– 0: "non-specific"

display_source_selector

– Selects the type of value that is displayed on the indication-/adjustement-module

– "0: ""Physical value"" 1: ""Percent value"" 2: ""Lin percent value"" 6: ""Out(AI1)"" 7: ""Level"" 8:

""Out(AI2)"" 9: ""Out(AI3)"""

max_peak_sensor_value

– Holds the maximum sensor value. Write access resets to current value. Unit derives from

'Sensor_range.unit'

– Write access resets to current value

min_peak_sensor_value

– Holds the minimum sensor value. Write access resets to current value. Unit derives from

'Sensor_range.unit'

– Write access resets to current value

CAL_POINT_HI

– Highest calibrated value. For calibration of the high limit point you give the high measurement

value (pressure) to the sensor and transfer this point as HIGH to the transmitter. Unit derives

from 'Sensor_range.unit'

CAL_POINT_LO

– Lowest calibrated value. For calibration of the low limit point you give the low measurement

value (pressure) to the sensor and transfer this point as LOW to the transmitter. Unit derives

from 'Sensor_range.unit'

CAL_MIN_SPAN

– Minimum calibration span value allowed. Necessary to ensure that when calibration is done,

the two calibrated points (high and low) are not too close together. Unit derives from 'Sensor_

range.unit'

SCALE_IN

– Min/max-adjustment: Upper and lower calibrated points of the sensor. Unit derives from

'Sensor_range.unit'

trimmed_value

– Sensor value after the trim processing. Unit derives from 'Sensor_range.unit'

sensor_sn

– Sensor serial number

temperature