10 Приложение

VEGASON 61 • Foundation Fieldbus

28790-R

U-130507

CURVE_STATUS

– Result of table plausibility check

SUB_DEVICE_NUMBER

SENSOR_ELEMENT_TYPE

display_source_selector

– Selects the type of value, which is displayed on the indicating and adjustment module

max_peak_sensor_value

– Holds the maximum sensor value. Write access resets to current value. Unit derives from

'Sensor_range.unit'

min_peak_sensor_value

– Holds the minimum sensor value. Write access resets to current value. Unit derives from

'Sensor_range.unit'

CAL_POINT_HI

– Min./max.-adjustment: Upper calibrated point of the sensor. It refers to 'Cal_level_hi'. The unit

is defined in 'Sensor_range.unit'hi

CAL_POINT_LO

– Min./max.-adjustment: Lower calibrated point of the sensor. It refers to 'Cal_level_lo'. The unit

is defined in 'Sensor_range.unit'

CAL_LEVEL_HI

– Min./max.-adjustment: Level at 'Cal_point_hi'. When writing 'Cal_level_hi' and 'Cal_type' = 1

(Online) the 'Cal_point_hi' is automatically set to the current sensor value. The unit is defined in

'Level_unit'

CAL_LEVEL_LO

– Min./max.-adjustment: Level at 'Cal_point_lo'. When writing 'Cal_level_lo' and 'Cal_type' = 1

(Online), the 'Cal_point_lo' is automatically set to the current sensor value. The unit is defined

in 'Level_unit'

CAL_TYPE

– Min./max.-adjustment: Defines type of calibration: Dry: no influence of sensor value. Online:

current sensor value determines 'Cal_point_hi/lo'

level

– Value after min./max. adjustment

level_unit

– Unit code of 'Level', 'Level_offset', 'Cal_level_hi', 'Cal_level_lo'

level_offset

– Offset that is added to the 'Level' value. Unit derives from 'Level_unit'

SENSOR_OFFSET

– Offset that is added to the 'Sensor_value'. Unit derives from 'Sensor_range.unit'

end_of_operation_range

– Set up to suit the process conditions

begin_of_operation_range

– Set up to suit the process conditions

product_type

– Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this

parameter cannot be written

liquids_medium_type

– Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this

parameter cannot be written

solids_medium_type

– Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this

parameter cannot be written

liquids_vessel_type

– Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this

parameter cannot be written