Инструкция по эксплуатации VEGA VEGACAL 66 Foundation Fieldbus

Страница 48

Advertising
background image

48

10 Приложение

VEGACAL 66 • Foundation Fieldbus

30038-R

U-131015

sensor_range

– "sensor_range.Units Index" is the unit for "sensor_value", "max/min_peak_sensor_value",

"Calibration Highest/Lowest Point" and "empty_vessel_ocrr_dist"

simulate_primary_value

simulate_secondary_value_1

simulate_secondary_value_2

Linearization Type

– Linearization Type, the selectable types are: Linear, User def; Cylindric lying container,

Spherical container

tab_op_code

tab_index

tab_max_number

tag_min_number

tab_actual_number

tab_status

tab_x_y_value

display_source_selector

– Selects the type of value, which is displayed on the indicating and adjustment module

max_peak_sensor_value

– Holds the maximum "sensor_value". The unit is defined in "sensor_range.Units Index"

min_peak_sensor_value

– Holds the minimum "sensor_value". The unit is defined in "sensor_range.Units Index"

Calibration Highest Point

– Min./Max. adjustment: this is the upper calibrated point of the sensor_value. It refers to "cal_

level_hi".

– The unit is defined in "sensor_range.Units Index"

Calibration Lowest Point

– Min./Max. adjustment: this is the lower calibrated point of the sensor_value. It refers to "cal_

level_lo".

– The unit is defined in "sensor_range.Units Index"

cal_level_hi

– Min./Max. adjustment: this is the value of level at "Calibration Highest Point". The unit is defined

in "level_unit.

– When writing "cal_level_hi" and "cal_type" = 1, the "Calibration Highest Point" is automatically

set to "sensor_value"

cal_level_lo

– Min./Max. adjustment: this is the value of level at "Calibration Lowest Point". The unit is defined

in "level_unit"

– When writing "cal_level_lo" and "cal_type" = 1, the "Calibration Lowest Point" is automatically

set to "sensor_value"

cal_type

– Min./Max. adjustment: this parameter defines the type of calibration:

– Dry: no influence of "sensor_value" on level calibration

– Online: current "sensor_value"determines "Calibration Highest/Lowest Point"

level

level_unit

level_offset

sensor_offset

phase_angle_select

– set up to suit the process conditions

epsilon_r

– set up to suit the process conditions

product_type