Инструкция по эксплуатации VEGA FIBERTRAC 31 Foundation Fieldbus

Страница 75

Advertising
background image

75

11 Приложение

FIBERTRAC 31 • Foundation Fieldbus

41780-R

U-130731

Hex

Quality

Sub-Status

Condition

0x44

Uncertain

Last Usable Value

Three or more internal communications have failed

while "Process Data Update". Last usable value is

displayed

0x48

Uncertain

Substitute

On user error codes: 29

0x4C

Uncertain

Initial Value

After startup of device or channel assignment

in AIFB was changed. The channel unit may be

unknown until next "Process Data Update"
On user error codes: 13

0x80

Good (NC)

Non-specific

No errors concerning to channel handling
On user error codes: 0, 33, 45, 71, 126, 127

Mapping of User Error Codes to FF Field Diagnostics

Priority

Description

User Error Codes

NE-107 Status

31

Hardware failure

40, 41

FAILURE

30

Memory failure

34, 35, 36, 37

FAILURE

29

Software failure

80

FAILURE

28

Paramererization corrupt

72

FAILURE

27

Undefined 27

-

-

26

Undefined 26

-

-

25

Paramererization error

16, 17, 25, 52, 53, 57, 66, 117,

120

FAILURE

24

Conflict in MGC

121, 122, 141

FAILURE

23

Communication error in MGC

8

FAILURE

22

MGC slave reports error

38

FAILURE

21

Undefined 21

-

-

20

Undefined 20

-

-

19

Undefined 19

-

-

18

Detector temperature critical

125

OUT_OF_SPEC

17

Error while auto-standardization

73

FAILURE

16

Excessive radiation

123, 124

FAILURE

15

Input out of bounds

13

OUT_OF_SPEC

14

Error while signal processing

68

FAILURE

13

Undefined 13

-

-

12

Undefined 12

-

-

11

Undefined 11

-

-

10

Undefined 10

-

-

9

Undefined 9

-

-

8

Undefined 8

-

-

7

AITB simulated

29

FUNCTION_CHECK

6

Undefined 6

-

-

Advertising