Installation Guide

JIP BaBV (PN25)

District Energy

VI.KD.D1.0H

DEN-SMT/SI

ENGLISH

1.0 Handling

1.1 Storage
- Storage temperature –20 to +65 °C dry;

free of dirt

- A desiccant or heating to prevent

condensation is necessary in damp
rooms.

- Don't damage the paintwork.

1.2 Transport
- Transport temperature –20 to + 65 °C.
- Protect against external force (impact,

vibration etc.).

- Don't damage the paintwork.

1.3 Handling before installation
- If flange covers are fitted, remove

shortly before installation!

- Protect against atmospheric conditions

e.g. wetness (use a desiccant).

- Correct handling protects against

damage.

2.0 Description

2.1 Scope of applications

Line regulating valves with a defined

characteristic for heating and cooling

systems. The plant designer is responsible

for selecting the correct valve for the

purpose.

Note: Do not use BaBV valves for handling

steam!

2.2 Operating principles

The flow is reduced (cone/seating function)

by turning the hand wheel clockwise.
- Position of the plug at DN 50 - 150 is

shown on two digit display. The outer
digit shows the basic setting and the
internal digit shows every tenth of the
turn.

3.0 Installation

General notes on installation:
The following points should be taken into

account besides the general principles

governing installation work:
- Remove flange covers if present.
- There must be no foreign bodies inside

the valve or piping.

- Valves can be installed with the spindle

pointing in any direction, but the
preferred spindle position is vertical.

- Reference for insulation:

If media-temperatures < ambient
temperatures - ask manufacturer.

- Installation upside down only if the

medium is clean.

- Connection flanges must be properly

aligned.

- All parts must be free from stress after

installation.

- The valve must not serve as a fixed

point. It must be carried by the piping.

- Protect the valve from dirt, especially

during construction work.

- Install compensators to compensate for

thermal expansion of the piping.

- It is forbidden to heat the valve to

above its service temperature (see
data sheets), for instance by welding,
grinding, etc.

- To ensure that flow settings are correct,

the pipe run should be straight for at
least 5D upstream and 2D downstream
of the valve.

4.0 Presetting and locking the
handwheel

Position of the plug is shown on two

digit display. The outer digit (a) shows
the basic setting and the internal digit
(b) shows every tenth of the turn.

Turn the hand-wheel clockwise to

minimum flow. Digital display shall
show 0,0. Turn the hand-wheel
counter clockwise to required value of
presetting by using the setting table.

DN 50-80: Optionally you can lock the

hand-wheel and protect the setting.
Thread the sealing wire (c) through
the holes on hand-wheel and secure it
around the handle. Fit the lead seal.

DN 100-150: Optionally you can lock

the hand-wheel and protect the setting.
Fit the enclosed clip (d) in the cut-out
in the hand-wheel. Thread the sealing
wire (c) through the holes on hand-
wheel and secure it around the handle.
Fit the lead seal.

Commissioning

Connect differential pressure meter
(f.e. PFM 4000/5000) to rectus nipples.
Pay attention to direction of the flow
to avoid wrong measurments of the
differential pressure. In order to safety
and properly make the commissioning,
follow the instructions of differential
pressure meter (f.e. PFM 4000/5000).