4 команды modbus rtu, Fc3 read holding register – Инструкция по эксплуатации VEGA VEGABAR 87 Modbus and Levelmaster protocol - Operating Instructions
Страница 67
67
10 Приложение
VEGABAR 87 • Протокол Modbus и Levelmaster
46297-R
U-131205
Register Name
Register Number
Type
Note
Status
2200
DWord
See Register 100
PV
2202
DWord
Primary Variable in Byte Order BACD (Middle Endian)
SV
2204
DWord
Secondary Variable in Byte Order BACD (Middle
Endian)
TV
2206
DWord
Third Variable in Byte Order BACD (Middle Endian)
QV
2208
DWord
Quarternary Variable in Byte Order BACD (Middle
Endian)
Unit Codes for Register 104, 108, 112, 116
Unit Code
Measurement Unit
32
Degree Celsius
33
Degree Fahrenheit
40
US Gallon
41
Liters
42
Imperial Gallons
43
Cubic Meters
44
Feet
45
Meters
46
Barrels
47
Inches
48
Centimeters
49
Millimeters
111
Cubic Yards
112
Cubic Feet
113
Cubic Inches
10.4 Команды Modbus RTU
FC3 Read Holding Register
Этой командой может считываться любое количество (1-127) регистров временного
хранения. Передается стартовый регистр, с которого должно начинаться считывание, и
число регистров.
Request:
Parameter
Length
Code/Data
Function Code
1 Byte
0x03
Start Address
2 Bytes
0x0000 to 0xFFFF
Number of Registers
2 Bytes
1 to 127 (0x7D)